INSTALLATION & OPERATION MANUAL
CW-H10, CW-H15, CW-H15S, CW-H15S Plus
MULTI-MAGIC MODELS
ORIGINAL ENGLISH INSTRUCTIONS
ILL1916
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 3
TABLE OF CONTENTS
Index
IMPORTANT SAFETY INSTRUCTIONS 4
COOLER VIEWS 6
CW-H10 MODELS 6
CW-H15 MODELS 7
COOLER CONTENTS 9
INSTALLATION COMPONENTS 9
OPTIONAL COMPONENTS 9
TECHNICAL DESCRIPTION 10
AIRFLOW 10
HEAT EXCHANGERS 10
TRANSPORT 11
MOVING THE COOLER 11
LIFTING THE COOLER 11
UNPACKING THE COOLER 11
INSTALLATION 12
COOLER LOCATION 12
ACCESS FOR SERVICING AND MAINTENANCE 12
MOUNTING/SUPPORT 12
VIBRATION ISOLATION 12
DRIP-TRAY 12
SUPPLY AIR DUCT CONNECTIONS 12
EXHAUST TRANSITION ASSEMBLY 13
EXHAUST DUCT CONNECTION REQUIREMENTS 13
SUPERCOOL COOLERS 14
ELECTRICAL REQUIREMENTS 15
ELECTRICAL SUPPLY INSTALLATION 15
MOTOR LOCKED-ROTOR PROTECTION 15
HIGH LEAKAGE CURRENT 15
RESIDUAL CURRENT CIRCUIT BREAKER (RCCB) 15
FIRE TERMINALS 15
WATER REQUIREMENTS 16
WATER SUPPLY INSTALLATION 16
WATER SUPPLY PRESSURE REGULATION 16
WATER SUPPLY ISOLATION 16
WATER SUPPLY FILTRATION 16
WATER HAMMER 16
WATER DRAIN INSTALLATION 16
COOLER CONTROL COMPONENTS 17
WATER MANAGEMENT SYSTEM 17
CONTROL COMPONENTS 17
INPUT AND OUTPUT TERMINALS 17
MULTI-MAGIC CONTROLS 18
MULTI-MAGIC PLC 18
CONTROL SCREEN 18
MONITOR SCREENS 19
SENSOR SCREEN 19
CONTROL METHOD OPTION 1 (W/C) 20
SETTING DEVICE NODE ADDRESS (W/C) 20
CONTROL METHOD OPTION 2 (MBS) 21
COMMUNICATION SETUP (MBS) 21
CONTROL METHOD OPTION 3 (BCN) 22
BACNET PROTOCOL SELECTION 22
BACNET MS/TP COMMUNICATION SETUP 22
BACNET IP COMMUNICATION SETUP 22
RS-485 NETWORK SETUP 23
RS-485 CABLE SPECIFICATIONS 23
RS-485 CABLE CONNECTIONS 23
RS-485 CABLE WIRING RULES 23
RS-485 TERMINATING RESISTORS 23
RJ45 ETHERNET SETUP 23
ETHERNET CABLE SPECIFICATIONS 23
ETHERNET CABLE WIRING RULES 23
CONTROL METHOD OPTION 4 (BMS) 24
BMS FAULT OUTPUT 24
BMS CONTROL INPUTS 24
BMS FAN SPEED INPUT 24
BMS CABLING REQUIREMENTS 24
CONTROL METHOD OPTION 5 (LCL) 25
MANUAL DRAIN 25
CHANGING COOLER SETTINGS 26
PRE-WET 26
FAN START DELAY & RUN OUTPUT RELAY 26
BMS LOCK SPEED 27
MESSAGE BAR CONTENTS 27
LED STATES 28
FAULT CODE DISPLAY 28
FAULT CODE RESET 28
FAULT CODE DESCRIPTIONS 29
COMMISSIONING 30
INSTALLATION CHECKLIST 30
SETUP MENU ACCESS 31
MULTI-MAGIC DEVICE TYPE 31
TEST MENU 31
WATER MANAGEMENT SYSTEM CHECKS 31
HEAT EXCHANGER FLUSH 31
SUPPLY FAN CHECKS 31
AIR FLOW BALANCING 32
MULTI-MAGIC COOLER SETTINGS 33
MULTI-MAGIC RS-485 SETTINGS 33
MULTI-MAGIC IP SETTINGS 33
CUSTOMER HANDOVER CHECKLIST 33
MAINTENANCE SCHEDULE 34
MAINTENANCE FREQUENCY 34
WINTER SHUTDOWN 34
MAINTENANCE CHECKLIST 35
MAINTENANCE INSTRUCTIONS 37
COOLER CONTROL 37
QUARTERLY INSPECTION PROCEDURES 37
INDIRECT & DIRECT PUMPS 38
WATER INLET SOLENOID VALVE 38
CHLORINATOR 39
WATER MANAGEMENT PROBE 39
WATER RESERVOIR (TANK) 39
DRAIN VALVE 40
INLET AIR FILTERS 40
INDIRECT HEAT EXCHANGERS 41
DIRECT HEAT EXCHANGERS (CHILLCEL) 42
TROUBLESHOOTING 43
WARRANTY TERMS (AUSTRALIA) 44
WARRANTY TERMS (USA) 48
APPENDIX A 52
EXAMPLE WALL CONTROLLER WIRING 52
APPENDIX B 54
EXAMPLE LOW VOLTAGE BMS WIRING 54
APPENDIX C 55
MODBUS REGISTERS 55
APPENDIX D 56
BACNET OBJECT LIST 56
4 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE.
FOR EUROPE
This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they
have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved. Children
shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
FOR AUSTRALIA, NEW ZEALAND & OTHER
NON-EUROPEAN COUNTRIES
This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they
have been given supervision or instruction
concerning use of the appliance by a person
responsible for their safety. Children should be
supervised to ensure that they do not play with
the appliance.
Means for all pole disconnection must be
incorporated in the xed wiring in accordance
with the wiring rules, adjacent to or on the
cooler cabinet. If mounting on the cooler
cabinet, take care not to puncture the water
reservoir.
The following specications for the cooler water
supply are required:
Water Connection ½” BSP (Aus/Eur), ½” NPT
(USA)
Min Water Pressure 100kPa (15psi)
Max Water Pressure 800kPa (115psi)
Max Water Flow 20 L/min (5.3 gallons/min)
Max Water Temperature 40°C (104°F)
This cooler is intended to be permanently
connected to the water mains and not
connected by a hose set.
If the supply cord is damaged, it must be
replaced by the manufacturer, its service agent
or similarly qualied persons in order to avoid a
hazard.
CAUTION: In order to avoid a hazard due to
inadvertent resetting of the thermal cut-out,
this appliance must not be supplied through an
external switching device, such as a timer, or
connected to a circuit that is regularly switched
on and o by the utility.
FOR AUSTRALIAN BUSHFIRE PRONE
AREAS
WARNING If this evaporative cooler is installed
in a BAL-12.5 to 29 area the evaporative cooler
dropper duct and ashings shall be adequately
sealed at the roof to prevent gaps greater than
3mm. The dropper duct and ashings shall be
non-combustible.
WARNING: This cooler is NOT APPROVED
for installation in any bushre zoned area/
property (BAL-12.5 to BAL-FZ).
WARNING - TO REDUCE THE RISK OF
FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended
by the manufacturer. If you have questions,
contact the manufacturer.
b) Before servicing or cleaning unit, switch
power o at service panel and lock the
service disconnecting means to prevent
power from being switched on accidentally.
When the service disconnecting means
cannot be locked, securely fasten a
prominent warning device, such as a tag, to
the service panel.
c) Installation work and electrical wiring
must be done by qualied person(s) in
accordance with all applicable codes and
standards, including re-rated construction.
d) When cutting or drilling into wall or ceiling,
do not damage electrical wiring and other
hidden utilities.
e) Do not use this fan with any solid-state
speed control device.
f) Ducted fans must always be vented to the
outdoors.
EMPLOYER AND EMPLOYEE
RESPONSIBILITIES
The installation and maintenance of evaporative
coolers at height has the potential to create
Occupational Health and Safety issues for
those involved. Installers are advised to ensure
they are familiar with the relevant State and
Federal legislation, such as Acts, Regulations,
approved Codes of Practice and Australian
Standards, which oer practical guidance on
these health and safety issues. Compliance
with these regulations will require appropriate
work practices, equipment, training and
qualications of workers.
Seeley International provides the following
information as a guide to contractors and
employees to assist in minimising risk whilst
working at height.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 5
As with any product that has moving parts
or is subject to wear and tear, it is VERY
IMPORTANT that you maintain your cooler
and have it regularly serviced. It is a condition
of warranty cover for your cooler that you
comply with all of the maintenance and
service requirements set out in this Manual.
Compliance with these requirements will
prolong the life of your cooler. Further, it is also
a condition of warranty cover that each item
in the Maintenance Schedule in the Manual is
lled out (by signing and dating it in the places
indicated) when the item is completed.
Any failure to carry out the required
maintenance and servicing, and any failure to
ll out the maintenance schedule, will void your
warranty.
MAINTENANCE NOTE
IMPORTANT SAFETY INSTRUCTIONS
INSTALLER AND MAINTENANCE
CONTRACTORS - RISK ASSESSMENT
Installer and Maintenance Contractors
A risk assessment of all hazardous tasks is
required under legislation. A risk assessment is
an essential element that should be conducted
before the commencement of work, to identify
and eliminate the risk of falls or to minimise
these risks by implementing control measures.
There is no need for this to be a complicated
process, it just is a matter of looking at the job
to be done and considering what action(s) are
necessary so the person doing the job does not
injure themselves.
This should be considered in terms of:
What are the chances of an incident
happening?
What could the possible consequence be?
What can you do to reduce, or better still,
completely get rid of the risk?
SOME POINTS TO CONSIDER
What is the best and safest access to the
roof and working areas?
If a worker is alone, who knows they are
there and if they get into diculty, how can
they summon help?
(Call someone on the ground? Mobile
phone? etc.)
What condition is the roof in? Should the
trusses, underside or surface be checked?
Does the worker have appropriate foot
wear? (Flat sole jogger type is advisable)
Are all power cables / extension leads safe
and appropriately rated?
Are all ladders, tools and equipment suitable
in good condition?
Where ladders are to be used, is there a
rm, stable base for them to stand on?
Can they be tied or secured in some way
at the top? Is the top of the ladder clear of
electricity supply cables?
Is there a roof anchor to attach a harness
and lanyard to? If so, instruction should be
issued for the use of an approved harness
or only suitably trained people used.
Are all tools and materials being used,
prevented from slipping and falling onto a
person at ground level? Is the area below
the work area suitably protected to prevent
persons walking in this area?
Does the work schedule take into account
weather conditions, allowing for work to be
suspended in high winds, thunder storms/
lightning or other types of weather giving
wet, slippery surfaces?
Is there an on-going safety check system of
harnesses, ropes, ladders and access/lifting
equipment and where they exist on roofs,
anchor points before the commencement of
work?
Is there a system which prevents employees
from working on roofs if they are unwell or
under the inuence of drugs or alcohol?
Are there any special conditions to consider
i.e. excessive roof pitch, limited ground
area, fragile roof, electrical power lines?
OTHER IMPORTANT REQUIREMENTS
Never force parts to t because all parts are
designed to t together easily without undue
force.
Never drill holes in the tank of the cooler.
Check the proposed cooler location, to
ensure that it is structurally capable of
supporting the weight of the cooler, or
provide an adequate alternate load bearing
structure.
Ensure the installation complies with all
local and national regulations with regards
to electrical, plumbing and bushre
construction requirements.
6 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
COOLER VIEWS
Dimensions are in mm (inches in brackets).
CW-H10 MODELS TOP
REAR SIDE
BOTTOM
ILL3156-A
ILL3157-A
ILL3158-A
ILL3159-A
ILL3161-A
FRONT
ILL3160-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 7
COOLER VIEWS
ILL1916
2290
[90.2]
1969
[77.5]
1825
[71.9]
1500
[59.1]
ILL1918
CW-H15 MODELS
TOP
REAR SIDE
BOTTOM
ILL1916-C
ILL1918-C
ILL1917-C
ILL1919-C
ILL1920-C
482
[19.0]
150
[5.9]
SUPPLY DUCT
500x500
(19.7x19.7)
668
[26.3]
419
[16.5]
509
[20.0]
1300
[51.2]
481
[18.9]
650 [25.6]
ILL1919
MOUNTING BASE
EXHAUST DUCT
1822 [71.7]
EXHAUST DUCT
217 [8.6]
1283
[50.5]
EXHAUST C/L
1171
[46.1]
MOUNTING BASE
1800 [70.9]
ILL2422
FRONT
ILL2422-C
50
[2.0]
400
[15.7]
800
[31.5]
1200
[47.2]
50
[2.0]
550
[21.7]
1150
[45.3]
1700
[66.9]
MOUNTING HOLES
10
[0.394]
TYP 16 PL
ILL1920
BASE FRAME UNDERSIDE
Dimensions are in mm (inches in brackets).
8 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
COOLER VIEWS
ILL2423-D
Item Description
1 AIR FILTER ASSEMBLY
2 ELECTRICAL ENCLOSURE
3 FAN GUARD
4 END PANELS
5 MOTOR AND FAN ASSEMBLY
6 INLET TRANSITION ASSEMBLY
7 PUMPS, DRAIN VALVE AND WATER PROBE
8 PUMPS, INLET SOLENOID VALVE AND CHLORINATOR
9 WATER TANK
10 BASE FRAME
11 SIDE PANELS AND ACCESS DOORS
12 OUTLET TRANSITION ASSEMBLY
13 SUPPLY DAMPER
14 INDIRECT HEAT EXCHANGER AND WATER SPREADERS
15 EXHAUST AIR GRILLE
16 LID ASSEMBLY
1
3
2
4
4
5
9
7
8
10
6
11
11
12
13
14
15
16
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 9
COOLER CONTENTS
INSTALLATION COMPONENTS
OPTIONAL COMPONENTS
Item
Seeley
Part
Description QTY
1A
1B
859749
862801
Cooler Installation, Operation, Maintenance Manual
Supercool Conversion Instructions (CW-H15S only)
1
2 861883 Adaptor Drain Elbow 1
3 866216 40mm Flexible Coupling 1
4 834798 Key, Control Box 1
5A
5B
637994
637393
Exhaust Centre Post CW-H15 or
Exhaust Centre Post CW-H10
1
6A
6B
6C
6D
6E
6F
6G
805597
804446
804422
864341
864385
864372
804579
Screw 8AB x ½” Pan Phill Stainless Steel
Screw SEMS HX 14x3/4"
Plastic Grommet Size 14
Screw Set SHCS Stainless Steel M6x35mm
Washer Flat Stainless Steel M6x12.5x1.2mm
Washer Flat Nylon M8x16mm
Blanking Grommet 12.7x17.5mm
10
5
5
4
4
4
2
7 931685 Exhaust Side Rails (1176mm Long) 2
8A
8B
834789
834790
Exhaust Grille (869x205) CW-H15 or
Exhaust Grille (571x247) CW-H10
1
9 637999 Exhaust Cap (CW-H15S Plus only) 2
Item
Seeley
Part
Description
1 121956 Multi-Magic Wall Control Kit
2A
2B
134192
134215
Roofstand 0-10
O
(CW-H10)
Roofstand 0-10
O
(CW-H15, H15S, H15S Plus)
3 121963 Multi-Magic Room Air Sensor Kit
4 121932 Multi-Magic Ambient Air Sensor Kit
5 121925 Multi-Magic Duct Air Sensor Kit
6 121918 Multi-Magic Pressure Sensor Kit
ITEM 1A ITEM 2 ITEM 3
ITEM 7
ITEM 8A/8B
ITEM 9
ITEM 10
ITEM 1
ITEM 2
ITEM 3A
ITEM 4
ITEM 3B
WARRANTY INFORMATION
DUCTED INDIRECT EVAPORATIVE
AIR COOLER
INTERNATIONAL
ILL2424-D
ITEMS &5A 5B
ITEMS A, B &D66 6
ITEMS E &F66
ITEM 4 ITEM 5 ITEM 6A ITEM 6B ITEM 6C
ITEM 6D ITEM 6E/F ITEM 6G
ITEM 7 ITEM 8
ITEM 9
ITEM 1B
ILL2426-A
ILL3803-A
ILL3709-A
ILL3709-A
ITEM 1
ITEM 3
ITEM 4 ITEM 5
ILL3867-A
ILL3962
ITEM 6
ITEM 2
10 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
TECHNICAL DESCRIPTION
AIRFLOW
The cooler has a single fan which draws hot outside air through
the rear-mounted air lters, through the dry channels of the air-
to-air indirect evaporative heat exchangers and into the plenum
at the front of the cooler.
Inside the plenum, the air is split into an exhaust ow and a
supply ow.
The exhaust air passes through the wet channels of the air-to-
air indirect evaporative heat exchangers and out through the
upper exhaust grille back to atmosphere.
The supply air passes over a secondary direct evaporative
cooling stage (Supercool cooler only), before entering the
customer's ductwork.
HEAT EXCHANGERS
Indirect Evaporative Cooling (IEC) Stage
All coolers have air-to-air indirect evaporative heat exchangers,
composed of alternating dry and wet channels separated by a
membrane. CW-H10 has 2 and CW-H15 has 3.
Through evaporation and conduction, heat is transferred from
the air in the dry channels, across the membrane, and into the
air in the wet channels.
The air in the dry channels is progressively cooled, but gains no
additional moisture.
Direct Evaporative Cooling (DEC) Stage
Supercool coolers are tted with a secondary direct evaporative
cooling stage.
The cooled air from the IEC stage passes over saturated
Chillcel® media, where, through evaporation, it is cooled further
with an increase in moisture content.
FAN
DEC STAGE
(SUPERCOOL
COOLERS)
IEC STAGE
SUPPLY AIR
EXHAUST AIR
FILTERS
INTAKE AIR
ILL3883
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 11
ILL1916
TRANSPORT
UNPACKING THE COOLER
The cooler will be delivered on a dedicated pallet and will be
wrapped in plastic lm which will need to be removed before
installation.
A small bag of installation components along with the exhaust
transition side rails and grilles can be found under the lid of the
main cabinet of the cooler. The exhaust transition will need to
be raised into place before operation.
WARNING: Once unwrapped, the exhaust transition assembly
should be tted together as soon as practicable to avoid loose
components becoming lost/damaged and/or a hazard.
MOVING THE COOLER
The cooler can be moved by forklift truck. Only use the
openings on the cooler. Do not lift through the pallet.
ILL1916-A
Min. forklift tyne gap
460mm (18.2”)
LIFTING THE COOLER
The cooler may be lifted by crane with slings through the cooler
base forklift truck tyne openings.
Do not attempt to lift using any cabinet features or by retrotting
lifting lugs. The cabinet may be damaged and/or lift safety
compromised.
It is recommended to use a spreader bar on the straps or slings
to protect the upper edges of the cooler with a corner protector
beneath the lifting straps to avoid any damage to the cabinet
during the lift.
12 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
The cooler base has a series of mounting holes for securing
the cooler. Dimensions and locations of the mounting holes are
shown in the cooler views at the beginning of this manual.
Where necessary, installers should use a sucient number of
suitably rated vibration isolation mounts to support the operating
mass of the cooler.
DRIP-TRAY
When coolers are installed indoors, or anywhere that water
leakage could cause damage, install a corrosion resistant drip
tray under the whole unit.
Recommended sizes:
CW-H10:
1500 x 1300 x 50mm (59” x 51” x 2”)
CW-H15, H15S, H15S PLUS:
1500 x 1900 x 50mm (59” x 75” x 2”)
Apply silicone sealant between drip-tray and cooler base at
every xing.
SUPPLY AIR DUCT CONNECTIONS
Dimensions for the supply air duct interface are shown in the
cooler views at the beginning of this manual.
Vibration absorbing exible connections are recommended for
all duct connections to the cooler.
All ducts must be independently supported.
All duct direction changes must utilise a generous radial turn
with internal air directors to minimise turbulence and maximise
eciency.
All ducts are to be suitably insulated to minimise temperature
losses.
INSTALLATION
MOUNTING/SUPPORT
Roofstands, accommodating 0-10 roof pitches, are available for
order via Seeley International. See Optional Components List.
ILL2426-A
ILL2426-A
COOLER LOCATION
Check the proposed cooler location, to ensure that it is
structurally capable of supporting the weight of the cooler, or
provide an adequate alternate load bearing structure.
Model Shipping Weight Operating Weight
CW-H10 250KG (550 LB) 255KG (560 LB)
CW-H15 340KG (750 LB) 330KG (728 LB)
CW-H15S, H15S Plus 355KG (783 LB) 345KG (761 LB)
Always locate the cooler where it will receive a plentiful supply
of fresh air, NOT in a recess where it may be starved for air or
where the air is polluted. Provision must be made for access to
electricity, water supplies and drains.
Air exiting the cooler exhaust is warm and heavily laden
with moisture. Ensure the cooler’s exhaust air will not cause
corrosion or damage to other nearby items. Do not allow
exhaust air to re-circulate into the air intake of the cooler.
Ensure the cooler location is a minimum of:
3.0m (10’) from a solid fuel heater ue
1.5m (5’) from a gas ue
• 1.0m (3.5’) away from adjacent solar panels or similar roof
mounted xtures
• 6.0m (20’) from a sewer vent
• 3.0m (10’) (preferably 5.0m (17’)) away from any TV antenna
or antenna cables. Make sure the cooler is not between the
antenna and the transmission tower that is providing the
television signal to the home.
ILL1925-A
Extra service or warranty charges may apply for the cost of any
equipment or additional labour involved in accessing the cooler
if these guidelines are not met.
Note! Do you need to discuss the installation of items like
safety anchor points with the customer?
ACCESS FOR SERVICING AND
MAINTENANCE
The cooler should be installed in a position that allows adequate
access for installation, and future maintenance and servicing
activities. This should comply with installation guidelines and
any local, State and National regulations.
Consider the following for installation location:-
Which has clear access to and around the cooler
Which is clear of xtures in line with below clearances
Which is clear of fall edges (> 3m (10') away)
Which is structurally capable of supporting the weight of the
cooler and service technicians
Required clearances around the cooler for future maintenance
and servicing are shown below.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 13
EXHAUST TRANSITION ASSEMBLY
The exhaust transition is supplied in knock-down form and it's
components are to be found beneath the lid of the cooler and
inside the component kit.
1. Unscrew the 6 x SCREW SEMS HEX 14 x 3/4” securing
the large top panel to the cooler body.
ILL2427-A
ILL2427-A
4. Fit the supplied 3 x PLASTIC GROMMET SIZE 14 to the
rear lid panel upstand square holes.
ILL2428-A
ILL2428-A
5. Fit the supplied 2 x PLASTIC GROMMET SIZE 14 to the
EXHAUST CENTRE POST.
ILL2429-A
ILL2429-A
6. Position the large top panel over the top of the cooler, with
the rear u-channel over the top of the upstand, the side
rails sitting on the tops of the cooler side walls and the
end posts sitting on the outside of the front tray.
ILL2430-A
ILL2428-A
7. Slip the 2 x EXHAUST GRILLE and 1 x EXHAUST
CENTRE POST into position, retained inside the top panel
front u-channel.
CW-H15S Plus ONLY: Before tting to the cooler, slide an
EXHAUST CAP over the back of each EXHAUST GRILLE.
The EXHAUST CAP covers the top portion of the EXHAUST
GRILLE, and is designed to optimise the CW-H15S Plus
performance.
ILL2431-A
8. Screw the exhaust transition assembly to the cooler body
with the supplied 11 x SCREW SEMS HEX 14 x 3/4” .
(
3 x Rear, 3 x Left, 3 x Right, 2 x Centre Post.)
9. Fit the supplied 4 x M6 x 35MM SET SCREW,
STAINLESS STEEL FLAT WASHER, NYLON FLAT
WASHER to the tops of both core access doors (2 each
side). Apply a liberal coat of anti-seize paste to the screw
thread prior to tment.
10. Fit the supplied 2x BLANKING GROMMETS to the open
holes in the lid sides (1 each side).
ILL2432-B
INSTALLATION
EXHAUST DUCT REQUIREMENTS
If required for indoor installations the exhaust air may be ducted
away from the cooler.
Dimensions for the exhaust outlet are shown in the cooler views
at the beginning of this manual.
When designing the exhaust duct please note the following;
• Access to the heat exchanger cores requires the removal of
the cooler lid/exhaust transition. Ensure any additional ducting
is readily removable and/or lightweight.
• Where an installation requires extended exhaust ducts, the
increase in static load should not exceed 20 Pa (0.08 in wg).
2. Lift the large top panel and locate;
2 x EXHAUST SIDE RAILS (1176mm Long)
2 x EXHAUST GRILLE
2 x EXHAUST CAPS (CW-H15S Plus Only)
3. Fit the EXHAUST SIDE RAILS to the inside vertical faces
of the large top panel with the supplied 10 x SCREW
PAN PHILLIPS 8AB*1/2” SS. Ensure the foam seal faces
down.
M6 x 35MM
DOOR SCREWS
& WASHERS
BLANKING
GROMMET
14 x 3/4"
BODY SCREWS
14 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
INSTALLATION
The CW-H Supercool coolers are tted with Chillcel pads,
providing additional Direct Evaporative Cooling (DEC).
They can be congured in two ways;
ILL3663-A
ILL3665-A
ILL2431-A
STEP 1 - EXHAUST CAPS
MODEL PERFORMANCE
Supply Airow
Rate
External Static
Pressure
CW-H15S 1100 L/s 120 Pa
3960 m3/h
2330 CFM 0.52 in.w.g.
CW-H15S Plus 1600 L/s 80 Pa
5760 m3/h
3390 CFM 0.32 in.w.g.
To correctly congure this cooler, ensure the following steps are
followed during the installation and commissioning process;
MODEL FIT EXHAUST CAPS?
CW-H15S NO
CW-H15S Plus YES
This CW-H cooler has been supplied with 2x Exhaust Caps
(P/N 637999), shipped loose under other exhaust components.
For CW-H15S PLUS ONLY slide an EXHAUST CAP over the
back of each EXHAUST GRILLE. The EXHAUST CAP covers
the top portion of the EXHAUST GRILLE and is designed to
optimise the CW-H15S PLUS performance.
FIT EXHAUST CAPS TO BACK OF EXHAUST GRILLE
STEP 2 - SET CORRECT DEVICE TYPE
MODEL CHANGE DEVICE TYPE?
CW-H15S YES
CW-H15S Plus NO - FACTORY DEFAULT
SETTING IS CORRECT
For CW-H15S ONLY access the SETUP menu on the PLC to
change DEVICE TYPE.
ILL3664-A
Push and hold the RIGHT
button until the password
screen is displayed.
Use the navigation LEFT/
RIGHT and UP/DOWN buttons
to enter password “7378” and
push OK to display the SETUP
screen.
Use the navigation UP/DOWN
buttons to move the cursor to
DEVICE TYPE and push OK
Push OK to activate the
MODEL eld.
Use the navigation UP/DOWN
buttons to select CW-H15S.
Push OK to save the setting.
Push and hold the LEFT
button to return to the previous
menu. Repeat until the display
returns to the “CONTROL”
menu.
All CW-H coolers require the supply air plenum pressure to
be correctly set. Follow the detailed instructions set out in the
Commissioning section of this manual.
STEP 3 - SET SUPPLY AIR PLENUM PRESSURE
MODEL PLENUM PRESSURE
CW-H15S 175 Pa (0.70 in.w.g.)
CW-H15S Plus 210 Pa (0.84 in.w.g.)
ILL3665-A
LOGIN
Enter Password
7378
7378
ILL3664-A
ILL3666-C
ILL3667-B
ILL3666-C
SETUP
DEVICE TYPE
COMMUNICATION
SERVICE
SETTINGS
ILL3667-B
DEVICE TYPE
PRODUCT
FAMILY
MODEL
VOLTAGE
CW-H
380-480V/3PH
CW-H15S
ILL3668-A
ILL3668-A
SUPERCOOL COOLERS
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 15
ELECTRICAL REQUIREMENTS
ELECTRICAL SUPPLY INSTALLATION
INSTALLATION OF THE COOLER MUST CONFORM
TO LOCAL ELECTRICAL RULES, REGULATIONS AND
STANDARDS.
It is a requirement of Seeley International that all coolers be
wired with a dedicated circuit and circuit breaker/fuse at the
distribution board.
A mains isolation switch, with all pole disconnection, shall be
furnished by the contractor and installed adjacent to the cooler.
IMPORTANT! There are specic models for regional voltages
and frequencies which are not interchangeable. Specically, the
fan motor(s), transformer(s) and pump(s) may be unique to the
voltage/frequency of supply.
See the cooler rating label for the correct electrical data. Before
connecting the device, make sure the power supply matches
the cooler voltage and frequency.
Electrical Supply Specication (50Hz Option):
380-415V / 50 Hz / 3N~ / 4.9A (FLA)
Electrical Supply Specication (60Hz Options):
440-480V / 60 Hz / 3~ / 9A (FLA) 11.5A (MCA) 15A (MOPD)
200-240V / 60 Hz / 3~ / 11A (FLA) 14.5A (MCA) 20A (MOPD)
200-240V / 60 Hz / 1~ / 8A (FLA) 10.5A (MCA) 15A (MOPD)
Mains power terminals are provided inside the electrical cabinet
with glands provided for cable entry.
MOTOR LOCKED-ROTOR PROTECTION
Due to the built-in motor locked-rotor protection, the starting
current (LRA) is equal to or less than the nominal current (FLA).
FIRE TERMINALS
A pair of terminals labelled "FIRE" are provided for integration
with a building re management system.
These terminals provide power to the cooler controls and are
supplied with a bridge.
To use with a building management system, remove the bridge
and connect the terminals through a NORMALLY CLOSED
relay which opens in a re event.
Interrupting power to the PLC will immediately stop all cooler
components, including fans.
HIGH LEAKAGE CURRENT
IMPORTANT! High leakage current. Earth connection
essential before connecting supply.
The cooler utilises a fan motor with a built in inverter drive. To
comply with EMC regulations these drives adopt EMC lters
that connect to the motor earth terminals. The normal lter
leakage current to earth may accumulate to a total leakage
current in excess of 10mA. For asymmetrical power systems or
if a phase fails, the leakage current can increase to a multiple of
the nominal value.
To comply with regulations and to prevent electric shock this
leakage current must be properly addressed.
In particular, the earth terminal at the mains power point of
connection must be properly connected and earthed. Power
must not be applied until this is correctly completed.
RESIDUAL CURRENT CIRCUIT BREAKER
(RCCB)
The cooler utilises a fan motor with a built-in variable speed
drive (VSD). If local electrical standards require the use of a
residual current circuit breaker (RCCB), only AC/DC-sensitive
residual current devices (type B) are permissible. If incorrectly
selected and/or sized, pulsed charging currents from the
capacitors in the integrated EMC lter can lead to the instant
tripping of RCCB when the cooler power supply is switched on.
3~ MAINS
TERMINALS
FIRE
TERMINALS
24VDC POWER SUPPLY
The cooler is provided with a 24VDC switch mode power
supply for use with internal components and optional sensor
accessories. The maximum power available for external
components is 30W.
TRANSFORMER TAPPINGS
440-480V / 3~ coolers ONLY are tted with a transformer to
power the cooler electronics. By default the input voltage
jumper is set for 480V. If the power supply has a dierent
phase-to-phase voltage, reposition the jumper as per the table
below.
380-415V control box shown
PHASE TO PHASE
PRIMARY VOLTAGE
JUMPER
BETWEEN
380V 31 - 38
400V 32 - 38
415V 31 - 37
440V 32 - 37
460V 32 - 36
480V 33 - 36
16 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WATER SUPPLY INSTALLATION
The cooler requires a permanent water supply to be
connected. A built-in Inlet Solenoid Valve, controlled by the
water management system, allows water into the cooler when
required.
INSTALLATION OF THE WATER SUPPLY MUST CONFORM
TO LOCAL PLUMBING RULES, REGULATIONS AND
STANDARDS.
The following specications for water supply are required:
Water Connections:
½” BSP (Aus/Eur), ½” NPT (USA) male.
Water Supply:
100kPa (15psi) - 800 kPa (115psi)
10L/min (2.6 gal/min) MINIMUM
20L/min (5.3 gal/min) RECOMMENDED
Water Supply Temperature:
40°C (105°F) MAXIMUM
Water Supply Salinity:
100 to 1150μS/cm
ILL1940-B
WATER REQUIREMENTS
WATER SUPPLY PRESSURE REGULATION
The Installer must provide a pressure regulator in the water
supply line adjacent to the cooler to regulate water supply
pressures between 100kPa (15 PSI) and 800kPa (115 PSI).
Important! Water pressures which are lower than 100kPa (15
PSI) will prevent the inlet solenoid valve from opening.
Important! Water pressures which are higher than 1200 kPa
(175 PSI) and/or water temperatures which are higher than
40ºC (105ºF) risk inlet solenoid valve failure.
Water pipes installed on the outside of a building, or any other
exposed location, shall have adequate insulation to protect
against freezing in the winter and solar radiation heating in the
summer.
If a non-return valve is installed in the water supply line, it
is recommended that a suitable pressure relief valve is also
installed between the cooler and the non-return valve to limit
the pressure rise associated with the heating eects of ambient
temperature and solar radiation.
WATER SUPPLY ISOLATION
The Installer must provide a manual 1/4 turn ball type shut o
valve (do not use a stop cock) in the water supply line adjacent
to the cooler, subject to local plumbing regulations. This allows
the water supply to be isolated whenever work needs to be
done on the cooler.
In areas where temperatures can cause water supply pipes
to freeze, a drain down facility should be provided during the
installation. This drain down facility must be activated prior
to freezing conditions to avoid possible damage to the cooler
components.
WATER SUPPLY FILTRATION
The Installer must provide an inlet water lter in the water
supply line, external to the cooler, to prevent any debris from
entering and damaging cooler components.
Important! Flush the water pipe to remove any contaminants
(swarf, lings or dirt) before nal tting. Contaminants can
lodge in the inlet solenoid valve, preventing it from functioning
correctly.
The cooler's water management system is designed to use
water that is suitable to be classied as ‘potable’ and t for
human consumption. If alternative water (including rain water) is
to be used that contains unusually high or low levels of salinity,
hardness, acidity or chemical contaminants, then additional
ltration or treatment systems should be employed to render the
water ‘potable’.
WATER HAMMER
Not all installation pipeworks are the same, and some may
require additional prevention against water hammer. If water
hammer is a problem, it is the responsibility of the Installer to t
an appropriate water hammer arresting device external to the
cooler.
WATER
INLET
WATER
DRAIN
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 17
WATER DRAIN INSTALLATION
The cooler requires a permanent water drain to be connected.
A built-in drain valve, controlled by the water management
system, releases water from the cooler when required.
INSTALLATION OF THE WATER DRAIN MUST CONFORM
TO LOCAL PLUMBING STANDARDS.
Drain Connections:
The cooler installation kit contains components to congure the
drain valve discharge to one of the following options:
- Down or Rear Discharge
- 1.5" (40mm) BSP Male or 1.5" Flexible Coupling.
Drain Rate:
15 L/min (4 gal/min)
Important! Water drained from the drain valve is high in salinity
and must be carried away to a suitable discharge point on the
building or property. Never drain the water directly onto the roof
ILL2442-E
ILL2442-E
ILL2443
The removable access panel should be re-assembled after
drain line installation.
Important! Drainage systems with long pipe runs, multiple entry
points, and/or incorporating traps shall use a tundish or similar
device to create a 25mm (1") air-gap between the bottom of the
drain valve and the drainage system.
ILL3938
WATER REQUIREMENTS
18 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
FAN SPEED MANAGEMENT SYSTEM
The cooler fan is driven by an electronically commutated DC
motor with integrated variable speed drives (VSD) that allows
for 0-10Vdc speed control.
The fan speed is controlled by the inputs from the Primary
Control Method (e.g. Multi-Magic Wall Controller). Depending
upon the control type, speed control is either continuously
variable or in 10 discrete speed steps (Speed 1-10).
If, when commanded to start, the fan start delay option is
enabled, the fan will remain o until the delay timer has expired.
Upon starting, the fan will initially run at a xed slow speed for
30 seconds before increasing to the requested speed.
If pre-wet is enabled, the supply fans will remain at the xed
slow speed until the pre-wet cycle is complete.
WATER MANAGEMENT SYSTEM
The cooler contains multiple parts to supply, distribute and
manage the water needed for the heat exchangers.
Water Inlet Solenoid Valve
The inlet solenoid valve allows water into the water reservoir. It
is open during the following phases.
Initial Tank Fill
Trigger: Entering IEC or DEC mode.
IEC Tank Fill
Trigger: Indirect Watering Cycle = TANK FILL.
DEC Only Tank Fill
Trigger: Low Probe = WET.
Once open, the inlet solenoid valve will remain open until the
water high probe has detected water for at least 5 seconds.
If the water drain valve is open, the inlet solenoid valve will
remain closed.
Indirect Pump Control (IEC Watering Cycle)
The indirect pumps move water from the reservoir to the 3
indirect heat exchangers.
The indirect heat exchangers do not require continuous
watering and the pump runs on the following cycle
Tank Level OK - Water lled to high probe and waiting for
next IEC pump cycle to start.
Indirect Pump Running (60 seconds).
Core Drain - IEC pump stopped and excess water is
draining back to the reservoir (1 minute 30 seconds)
Tank Fill - IEC pump stopped and inlet solenoid valve open
and re-lling to high probe (6 minutes 30 seconds)
Total IEC pump on time = 1 minute
Total IEC pump o time = 8 minutes
Direct Pump Control (Supercool coolers only)
The direct pump moves water from the reservoir to the Chillcel®
media. When running in DEC mode the direct pump runs
continuously. Excess water from the Chillcel® media drains
back to the reservoir.
COOLER CONTROL COMPONENTS
Water Salinity Control
As water evaporates from the heat exchangers, the salinity of
the remaining water naturally increases.
The water management system uses the 3-pin water probe to
measure water conductivity as a proxy for salinity. The probe
can sense conductivity down to 9 µS (about 4ppm) .
Water conductivity is updated every time water reaches the high
probe and, when it exceeds the upper set point, a salinity drain
cycle will start.
Chlorinator Control
The chlorinator is composed of specially treated plates. When
energised and submerged in water, electrical current ows
between the plates generating chlorine which is known to kill
bacteria in water supplies.
The chlorinator is active when the cooler is in IEC mode, AND
the water level is above the bottom probe AND the water
conductivity is >1500 µs/cm.
If the water conductivity remains <1500µs/cm for 24 hours, a
clean tank drain cycle will start.
Water Tank (Reservoir) Drain Valve
The drain valve will automatically open when power is rst
applied to the cooler. It will close again when IEC or DEC mode
is enabled.
During a salinity drain cycle, the drain valve opens until the
water level falls below the low probe, then the drain valve
closes immediately, and inlet solenoid valve opens to rell the
reservoir with fresh water.
During a clean water drain cycle, the drain valve remains open
for 10 minutes, after which the inlet solenoid valve opens to rell
the reservoir with fresh water.
The drain valve will open if it has been 3 days since IEC or DEC
mode was last run.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 19
CONTROL COMPONENTS
Cooler logic and controls are handled by a PLC in conjunction
with a Water Manager PCBA, both located in the controls
enclosure.
PLC
WATER MANAGER
PCBA
INPUT AND OUTPUT TERMINALS
A series of input and output terminals are located on the door of
the controls enclosure.
See MULTI-MAGIC CONTROLS for terminal functions.
COOLER CONTROL COMPONENTS
ILL3940
20 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MULTI-MAGIC CONTROLS
MULTI-MAGIC PLC
ILL3622-A
10
6
1
2
3
4
5
7
8
9
Item Description Item Description
1
UP – moves cursor up to next
variable or increase value in
edit mode
6 Green LED – Power Status
2
DOWN – moves cursor down to
next variable or decrease value
in edit mode
7
Red LED – Fault Status.
Number of ashes indicates
fault code
3 RIGHT – opens the next page 8 Yellow LED
4
LEFT – opens the previous
page
9
Green LED – Flashes if wall
control/MODBUS primary is
connected
5 OK (ENTER) – select/edit value 10
USB Type A for USB memory
stick
ILL3622-A
Use the navigation LEFT/RIGHT buttons to switch between
the “CONTROL”, “MONITOR”, “SENSORS” and "HISTORY"
screens.
To return to the previous menu screen long press the LEFT
button
CONTROL SCREEN
This screen allows the user to select the cooler's primary input
control method, including controlling the cooler manually from
the PLC via Local Mode.
For all PLC screens:
• Use the navigation UP/DOWN buttons to scroll through the
options
• Push the OK button to edit the option.
• Use the UP/DOWN buttons to change the value of the option.
Push the OK button again to conrm the selection and exit
edit mode.
ILL3624
Item Description Item Description
1
Primary Input Control Method;
LOCAL
WALL = Multi-Magic Wall Controller
BMS = Low Voltage BMS
Modbus
BACnet
4 PLC Software Revision
2
Cool Mode
Vent = Fan only.
Indirect = Fan & Indirect Evaporative
Cooling
Direct = Fan & Direct Evaporative
Cooling*
Supercool = Fan & Indirect & Direct
Evaporative Cooling*
5
Message Bar. Shows
current cooler status.
3
Fan Speed
If Control Method = Local; Sets Fan
Speed 0-10
Otherwise display 0-100% (BMS /
MODBUS)
or display 0-10 (Wall Controller /
BACnet)
6
Fault.
Displays if a fault condition
is active.
*NOTE. Direct Cool Mode and Supercool Mode are available for
Supercool enabled coolers only.
IMPORTANT! The cooler can only accept control inputs from
the one primary control method selected on the CONTROLS
screen, however control outputs are available to be read across
all methods.
For example, when Wall Controller is selected, the cooler will
only accept inputs (e.g. Fan Speed) from a Multi-Magic Wall
Controller, whereas outputs (e.g. Drain Valve status) can be
read by a 3rd party Modbus device.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 21
MULTI-MAGIC CONTROLS
MONITOR SCREENS
These screens allows the user to see the status of the cooler
components.
ILL3623
Item Description Item Description
1
Displays status of the
Inlet Water Solenoid Valve.
Image shows running water
into tank when valve is open.
3
Displays status of the
Drain Valve. Image shows
water emptying from tank when
valve is open.
2
Displays the tank water level.
Image empty when water not
detected at low probe.
Image half full when water
detected at low probe only.
Image full when water detected
at both low and high probes.
4
Displays the status of the
pumps.
Image shows owing water
when the Indirect Pump (IEC)
and/or Direct Pump (DEC) is
running.
SENSOR SCREENS
These screens allow the user to congure up to four 0-10Vdc
input channels, labelled S1 to S4, for use with optional sensor
accessories.
Tag Description
Ambient Air Sensor
AMBNT-T Temperature, 0-10V, -40...+70C or -40...+158F
AMBNT-H Relative Humidity, 0-10V, 0...100% rh
Room Air Sensor
ROOM-T Temperature, 0-10V, 0...+50C or +32...+122F
ROOM-H Relative Humidity, 0-10V, 0...100% rh
Supply Air Duct Sensor
SPLY-T Temperature, 0-10V, 0...+50C or +32...+122F
SPLY-H Relative Humidity, 0-10V, 0...100% rh
Dierential Air Pressure Sensor
PRESSURE Pressure, 0-10V, 0....+500Pa or 0....+2.00"wg
Temperature and Relative Humidity sensors require two input
channels. When conguring the rst channel for Temperature,
the second channel is automatically congured for Relative
Humidity.
Pressure sensors require only one input channel.
Installing sensor accessories does not automatically activate
additional sensor functionality. Customers require a control
method (e.g. Multi-Magic Wall Controller or 3rd Party Building
Management System) to use the measured values as required.
See separate Installation Instructions for each type of sensor for
example functions.
ILL3710-C
HISTORY SCREENS
These screens allow the user to view time stamped records
of the coolers fault code history and water drain history Each
history can be reset by selecting the CLEAR button.
ILL3930
Item Description Item Description
1
Displays water salinity level
(µS/cm) measured by 3 pin
probe.
3
Water Manager PCBA Software
Revision
2
Displays status of the
Chlorinator. ON/OFF
OK
FAULT
4
Displays PWM of the
Chlorinator 0...100%
ILL3870
Item Description Item Description
1
Displays the status of the fan
motors.
0-10Vdc analogue output from
the PLC to the supply fan (SF)
2
CW-H Supply Fan (SF) Status
OK
FAULT
ILL3931
22 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 1 (WALL)
MULTI-MAGIC WALL CONTROLLER (WALL)
The Multi-Magic Wall Controller,
(supplied separately) can control
up to a maximum of 15 Multi-
Magic coolers acting as a Primary
Controller over a Modbus RS-485
network.
It incorporates sensors to
automatically regulate local zone
temperature and relative humidity.
Ensure "WALL" is selected on the
CONTROL screen.
ILL3872
Push and hold the RIGHT
button until the password
screen is displayed.
Use the LEFT/RIGHT
and UP/DOWN buttons
to enter password “7378”
and push OK to display
the SETUP screen.
Use the UP/DOWN
buttons to select
COMMUNICATION and
push OK.
Use the UP/DOWN
buttons to select NODE
ADDRESS.
Push OK to activate the
eld.
Use the UP/DOWN
buttons to set a unique
value from 1 to 15 for each
cooler and push OK.
Note:
Baud Rate must be 38400
Parity must be NULL
Use the UP/DOWN
buttons to select SAVE.
Push OK to activate the
eld.
AFTER CHANGING
NODE ADDRESS, CYCLE
POWER TO COOLER TO
SAVE CHANGE.
Once set, the cooler
NODE ADDRESS
will appear on the
CONTROLS page.
SETTING DEVICE NODE ADDRESS (WALL)
When using the Multi-Magic Wall Controller, each cooler on the
RS-485 network requires a unique Node Address.
Refer to the RS-485 wiring rules section in this manual for
communication cable installation instructions and refer to
installation literature provided with the Multi-Magic Wall
Controller for additional setup instructions.
ILL3665
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 23
MULTI-MAGIC CONTROLS
The basic functions of cooler can be controlled via a 3rd Party
Modbus RS-485 Primary Controller.
Ensure "MOBUS" is selected on the CONTROL screen.
Modbus control registers are available for.
Vent Mode
IEC Cool Mode
DEC Cool Mode*
Fan Speed (0-100%)
Fault Code Reset
Manual Drain
*Note: DEC Cool Mode only operates on Supercool coolers
Additional read only registers are available for monitoring the
status of the connected coolers. See Appendix C for the full
register list.
Refer to the RS-485 wiring rules section in this manual for
communication cable installation instructions
CONTROL METHOD OPTION 2 (MODBUS)
3rd PARTY MODBUS RS-485 PRIMARY CONTROL
ILL3743
Use the LEFT/RIGHT
and UP/DOWN buttons
to enter password “7378”
and push OK to display
the SETUP screen.
Use the UP/DOWN
buttons to select
COMMUNICATION and
push OK.
Use the UP/DOWN
buttons to and push OK
to activate the available
elds.
Set a unique NODE
ADDRESS from 1 to 99 for
each cooler.
Set BAUD RATE and
PARITY values to match
the Primary Modbus
Controller.
Once nished select
SAVE.
Push OK
AFTER CHANGING
COMMUNICATION
SETTINGS, CYCLE
POWER TO COOLER TO
SAVE CHANGE.
Once set, the cooler
NODE ADDRESS
will appear on the
CONTROLS page.
COMMUNICATION SETUP (MODBUS)
All secondary devices (coolers) on the Modbus RS-485 network
requires a unique Node Address and communication setting
which match the 3rd Party Primary Controller.
Push and hold the RIGHT
button until the password
screen is displayed.
ILL3904
24 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MULTI-MAGIC CONTROLS
The basic functions of cooler can be controlled via BACnet
using either BACnet MS/TP or BACnet IP protocols.
Ensure "BACNET" is selected on the CONTROL screen.
BACnet control objects are available for.
Cooler ON/OFF
Vent Mode
IEC Cool Mode
DEC Cool Mode (Supercool only)
Fan Speed (0-10)
Fault Code Reset
Manual Drain
Additional monitoring objects are available for the status of the
connected coolers. See Appendix D for the full object list.
CONTROL METHOD OPTION 3 (BACNET)
3rd PARTY BACnet MS/TP or BACnet IP PRIMARY CONTROL
ILL3905
ILL3906
Push and hold the RIGHT
button until the password
screen is displayed.
Use the LEFT/RIGHT
and UP/DOWN buttons
to enter password “7378”
and push OK to display
the SETUP screen.
Use the UP/DOWN
buttons to select
COMMUNICATION and
push OK.
Use the LEFT/RIGHT and
UP/DOWN buttons to
1. Select either BACnet
MS/TP or BACnet IP
BACNET PROTOCOL SELECTION
ILL3907
BACNET MS/TP COMMUNICATION SETUP
BACNET IP COMMUNICATION SETUP
ILL3908-A
Note. Only one BACnet protocol may be active at a time.
With BACnet MS/TP
selected.
Use the UP/DOWN
buttons to set a unique
DEVICE ID from 1 to 99
for each cooler.
Press RIGHT button.
Set BAUD RATE and
PARITY values to match
the BACnet Controller.
Once nished, select
SAVE.
Push OK
AFTER CHANGING
COMMUNICATION
SETTINGS, CYCLE
POWER TO COOLER TO
SAVE CHANGE.
With BACnet IP selected
Use the UP/DOWN
buttons to set a unique
DEVICE ID from 1 to 99
for each cooler.
Press RIGHT button.
Set a unique Ethernet IP
ADDRESS for each cooler.
Set GATEWAY, NETMASK
ADDRESS, and IP PORT
to match the BACnet
Controller.
Once nished, select
SAVE.
Push OK
AFTER CHANGING
COMMUNICATION
SETTINGS, CYCLE
POWER TO COOLER TO
SAVE CHANGE.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 25
RS-485 NETWORK SETUP
The Multi-Magic Wall Controller, 3rd Party MODBUS and
BACnet MS/TP control options all use the RS-485 serial
protocol.
RS-485 CABLE SPECIFICATIONS
The Installer must supply communication cable between the
primary controller and connected coolers to the following
specication.
• Suitable for RS-485 applications
• Minimum 1 twisted pair (TP) and a third conductor
• Copper conductors
• 0.5 mm
2
/ AWG 20
• Braided shield with drain wire
Characteristic impedance 120Ω
• Nominal capacity between conductors 89 pF/m
• Nominal capacity between conductors and shielding 161pF/m
Note: Non-shielded cables are not protected against
electromagnetic interference which can cause signal
degradation.
ILL3705-B
RS-485 CABLE WIRING RULES
The following rules must be applied when setting up a RS-485
network:
• Communication wiring must be kept separate from AC power
wiring.
• Always route communication cables at least 300mm (12”)
away from high voltage cables and high-power machines.
• Crossover high power cables at right angles.
Maximum cable length from Wall Controller / Primary to rst
cooler is 100m (330ft).
• Maximum cable length between each cooler is 100m (330ft).
• Coolers must be connected in daisy-chain style, not star or
multi-drop..
RS-485 CABLE CONNECTIONS
The RS-485 serial terminals are located on the inside of the
control enclosure door.
Use the twisted pair for the ‘+’
and ‘-‘ signal terminals.
Use the 3rd conductor for the
signal GND terminals.
Attach the braided shield / drain
wire to the EARTH point at one
end only.
MODBUS RS-485 Terminal Details
Type Push-In
Stripping Length 8 mm - 10 mm / 5/16" - 3/8"
Cable Termination Ferrule with plastic sleeve
2x Conductors Cross Section (Flexible) 0.5 mm
2
/ 20 AWG
MULTI-MAGIC CONTROLS
RS-485 TERMINATING RESISTORS
Daisy-chained RS-485 networks require two 120Ω terminating
resistors, one at the start and one at the end of the
communication chain.
Attach a 120Ω terminating resistor between the "+" and "-"
terminals on the Primary Controller (e.g. Wall Controller)
Attach a 120Ω terminating resistor between the "+" and "-"
terminals on the last cooler on the network.
Do not t a 120Ω terminating resistor to coolers installed
between the Primary Controller and the last cooler.
ILL3677-B
See Appendix A for an example wiring schematic.
ILL3888-A
RJ45 ETHERNET SETUP
The BACnet IP (BCN) control option uses the RJ45 ethernet
port, located on top of the Multi-Magic PLC.
ETHERNET CABLE SPECIFICATIONS
The Installer must supply ethernet cable between the primary
controller and connected coolers to the following specication.
• Cat 5, 5e, 6 or 6e shielded
ETHERNET CABLE WIRING RULES
• Maximum single cable length between devices is 100m.
• Each cooler has a single RJ45 ethernet port, so an ethernet
switch or router is required
ILL3909-A
26 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
ID TYPE FUNCTION
FAULT
DIGITAL OUTPUT
DRY CONTACT
Fault Output. Congurable
NC or NO. See Settings
FAULT
BMS GND GROUND
BMS SPD
ANALOGUE INPUT
0-10Vdc
Fan Speed Input
BMS IEC
DIGITAL INPUT
DRY CONTACT
Cooler Operating Mode. See
Logic Table
BMS DEC
DIGITAL INPUT
DRY CONTACT
MULTI-MAGIC CONTROLS
BMS CONTROL INPUTS
The cooler operating mode is set via the IEC, DEC and SPD
input terminals with the following logic.
PRIMARY
CONTROL
METHOD
COOLER FUNCTION
IEC
TERMINAL
DEC
TERMINAL
SPD (Vdc)
TERMINAL
BMS OFF FALSE FALSE 0
BMS VENT FALSE FALSE >1.3
BMS INDIRECT COOL ONLY TRUE FALSE >1.3
BMS DIRECT COOL ONLY* FALSE TRUE >1.3
BMS INDIRECT & DIRECT COOL TRUE TRUE >1.3
BMS CLEAR FAULT FALSE FALSE
0.9 - 1.3 for
10 seconds
BMS MANUAL DRAIN FALSE FALSE
0.5 - 0.9 for
10 seconds
W/C VENT FIXED LOW SPEED TRUE FALSE N/A
W/C VENT FIXED HIGH SPEED FALSE TRUE N/A
*Note: DEC Cool Mode only operates on Supercool coolers
Warning: The BMS IEC and DEC input terminals are non-
isolated dry contacts. Do not apply an external power supply,
instead use a switch to connect the input terminal to the BMS
GND terminal.
BMS FAN SPEED INPUT
The cooler fan speed is set by applying an analogue 0-10Vdc
signal to the Fan Speed Input terminal, with the following logic;
BMS FAN SPEED
MINIMUM VOLTAGE MAXIMUM VOLTAGE
Vdc Vdc
OFF 0.00 1.29
1 1.30 1.79
2 1.80 2.69
3 2.70 3.59
4 3.60 4.49
5 4.50 5.39
6 5.40 6.29
7 6.30 7.19
8 7.20 8.09
9 8.10 8.99
10 9.00 10.00
BMS CABLING REQUIREMENTS
To avoid signal degradation use shielded, properly grounded
cables for all analogue and digital inputs and outputs. Route
input and output cables separately from high voltage power
cables. Interconnection wiring shall be separated by reinforced
insulation to any live parts.
See Appendix B for an example BMS wiring schematic.
BMS Terminal Details
Type Push-In
Stripping Length 8 mm - 10 mm / 5/16" - 3/8"
Cable Termination Ferrule with plastic sleeve
2x Conductors Cross Section (Flexible) 0.5 mm
2
/ 20 AWG
The basic functions of cooler can be controlled via a low voltage
Building Management System and the series of terminals
located on the control enclosure door. Ensure "BMS" is selected
on the CONTROL screen.
ILL3681
CONTROL METHOD OPTION 4 (BMS)
LOW VOLTAGE BUILDING MANAGEMENT SYSTEM
BMS FAULT OUTPUT
The fault output is a pair of dry contact terminals which can be
used to switch an external power supply.
Maximum Voltage: 250 Vac
Maximum Current: 3A
Minimum Switching Capacity: 100mA / 5Vdc
The fault output can be congured to be Normally Open (close
in Fault state) or Normally Closed (open in Fault state). See the
Commissioning Section for instructions on how to set.
The output is available for use in all Primary Control Methods,
not just BMS. For example, a Wall Controller can be used for
local zone control, with the fault signal monitored by a central
building management system.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 27
MULTI-MAGIC CONTROLS
The basic functions of cooler can be manually controlled from
the CONTROL screen. This mode is recommended for initial
setup and servicing only.
Ensure "LOCAL" is selected on the CONTROL screen.
Select the required COOL-MODE
• Vent = Fan only.
• Indirect = Fan & Indirect Evaporative Cooling
• Direct = Fan & Direct Evaporative Cooling*
• Supercool = Fan & Indirect & Direct Evaporative Cooling*.
For all modes, set the SPEED between 0 and 10 to run the fan.
*Note: Direct and Supercool Mode only operates on Supercool
coolers.
ILL3682
CONTROL METHOD OPTION 5 (LOCAL)
PLC LOCAL CONTROL
MANUAL DRAIN
All control modes provide an option to complete a manual tank
drain.
When triggered, the drain valve will open and stay open for at
least 10 minutes.
During this period, all pumps will stop and the inlet solenoid
valve will remain closed, however the fan will continue to run at
the requested speed.
Once triggered, it is not possible to close the drain valve again
until the 10 minutes as elapsed.
After 10 minutes the cooler will resume running in requested
operating mode.
ILL3910
To start a Manual Drain select the button under the tank icon on
the MONITOR-TANK screen.
FREEZE PROTECTION
When a Multi-Magic Ambient Sensor is installed, the Freeze
Protection function is automatically enabled.
When the ambient temperature is measured below 5
o
C (41
o
F)
for 20 minutes freeze protection mode is enabled.
Once enabled, the drain valve will open, all pumps will stop and
the inlet solenoid valve will remain closed, however the fan will
continue to run at the requested speed.
Once the ambient temperature is measured above 5
o
C (41
o
F)
for 20 minutes freeze protection mode will be deactivated and
the cooler will resume running in requested operating mode.
28 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MULTI-MAGIC CONTROLS
IEC
CHANGING COOLER SETTINGS
Push and hold the RIGHT
button until the password
screen is displayed.
Use the navigation LEFT/
RIGHT and UP/DOWN buttons
to enter password “7378” and
push OK to display the SETUP
screen.
Use the navigation UP/DOWN
buttons to move the cursor to
SETTINGS and push OK.
Use the navigation LEFT/
RIGHT buttons to move
between Pages 1, 2 and 3.
Use the navigation UP/DOWN
buttons to move the cursor to
the required setting.
Push OK to activate the eld.
Use the navigation UP/DOWN
buttons to set a unique value.
Push OK to save the setting
Long press LEFT to return to
the previous screen.
PRE-WET
Upon cooler start-up, Pre-Wet rst ensures the water tank is full
and then runs an extra 6-minute start up pump cycle to saturate
the heat exchanger cores.
During this Pre-Wet phase, the supply fan will be restricted to
Speed 1 regardless of controller input.
Pre-Wet ensures only cooled air is delivered, at the expense of
a longer start up time.
The Pre-Wet sequence will run again if the pumps have not run
in the last 30 minutes.
FAN START DELAY & RUN OUTPUT
RELAY
The Fan Start Delay can be a positive or negative timer.
If a positive timer is selected, the fan run output relay changes
state but the fan does not start until the timer has expired.
For example, this can be used to open or close 3rd party
dampers before the cooler fans start.
If a negative timer is selected, the fans start when requested,
but the fan run output relay does not change state until the timer
has expired.
For example, this can be used to ensure internal building
pressure is maintained before opening 3rd party relief vents.
IEC
USER SELECTABLE
-30s, -60s, -90s, -120s
RELAY OUTPUT
USER SELECTABLE
N/C or N/O
The fan run output is a pair of dry contact terminals which can
be used to switch an external power supply.
Maximum Voltage: 250 Vac
Maximum Current: 3A
Minimum Switching Capacity: 100mA / 5Vdc
The fan run output can be congured to be Normally Open
(close in when fan runs) or Normally Closed (open when fan
runs).
The output is available for use in all Primary Control Methods,
FAN SPEED INPUT
FAN RUN
SETTING VALUES
LANGUAGE
English (Default)
Spanish
Italian
French
Portuguese
PRE-WET
Enabled
Disabled (Default)
SALINITY DRAIN SET POINT
4275 uS/cm (Default)
2305 uS/cm
BMS FAULT STATE OUTPUT LOGIC
Normally Open (Default)
Normally Closed
SENSOR UNITS
Metric (Default)
Imperial
DATE TIME
Set for use with Fault Codes and Drain
History
FAN START DELAY
0s (Default)
-120s, -90s, -60s, -30s
+30s, +60s, +90s, +120s
FAN RUN OUTPUT LOGIC
Normally Open (Default)
Normally Closed
BMS LOCK SPEED
HIGH: 0-10 (Default 0)
LOW: 0-10 (Default 0)
FAN SPEED INPUT
RELAY OUTPUT
USER SELECTABLE
N/C or N/O
FAN RUN
ILL3678
USER SELECTABLE
+30s, +60s, +90s, +120s
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 29
MULTI-MAGIC CONTROLS
MESSAGE BAR CONTENTS
The MESSAGE BAR contains useful information about the
current cooler state.
The MESSAGE BAR will cycle through all active messages.
MESSAGE DESCRIPTION
STANDBY
Cooler is ON but no control input
active.
VENT MODE
Fan is running but no cooling stage
is on.
TANK INITIAL FILL
Inlet Water Solenoid is on and water is
entering the tank. Pumps will not start
until the tank is full.
PRE-WET FS LIMITED
Pre-Wet is enabled. The pumps are
running for an extra 6 minutes whilst
the fan speed is limited.
FAN START DELAY
Fan start delay is enabled. Fans will
start after the delay timer has expired.
INDIRECT PUMP RUNNING
IEC COOL MODE
IEC pump is running. Pump cycles
ON for 60 seconds and OFF for 100
seconds.
CORE DRAIN
IEC COOL MODE
IEC pump have just turned OFF and
water is returning back to tank.
TANK FILL-IEC
IEC COOL MODE
Inlet Water Solenoid is on and water is
entering the tank.
TANK LEVEL OK
IEC COOL MODE
Tank is full, waiting for IEC pumps to
start.
TANK FILL-DEC
DEC COOL MODE
Inlet Water Solenoid is on and water is
entering the tank.
DIRECT PUMP RUNNING
DEC COOL MODE
DEC pump is running. Pump runs
continuously.
SALINITY DRAIN
Tank water has reached the maximum
salinity level and a partial tank drain
and ll cycle is in progress.
CLEAN WATER DRAIN
The chlorinator has not run for 24
hours and a complete tank drain and ll
cycle is in progress.
TANK DRAIN
3-day tank drain delay or manual drain
triggered.
FREEZE PROTECTION
The tank has drained to prevent water
freezing.
REMOTE SHUTDOWN
Multi-Magic Wall Controller has been
locked by a BMS input. Refer to Wall
Controller manual.
BMS LOCK HIGH SPEED
Multi-Magic Wall Controller has been
locked by a BMS input to VENT Mode
Refer to Wall Controller manual.
BMS LOCK LOW SPEED
Multi-Magic Wall Controller has been
locked by a BMS input to VENT Mode
Refer to Wall Controller manual.
BMS LOCK SPEED
BMS Lock is a special mode for use with a Multi-Magic Wall
Controller.
When Wall Controller is selected as the Primary Control
Method, use the BMS IEC or DEC input terminals on any
connected cooler to remotely lockout the Wall Controller.
When applied, no cooler control from the Wall Controller is
possible and the cooler can be congured to either shutdown or
run in VENT mode at one of two dierent xed speeds
For example, if low speed is set to 3 and high speed is set to 8.
LOW SPEED
SETTING
(0-10)
HIGH SPEED
SETTING
(0-10)
IEC
TERMINAL
DEC
TERMINAL
COOLER
FUNCTION
0 0 FALSE TRUE SHUTDOWN
0 0 TRUE FALSE SHUTDOWN
0 0 TRUE TRUE SHUTDOWN
3 8 TRUE FALSE VENT SPEED 3
3 8 FALSE TRUE VENT SPEED 8
This feature may be useful when Building Managers wish
to remotely shutdown coolers during certain hours, enable
overnight building purges or when Climate Wizard products are
used as blowers for in line heaters during the winter season.
For groups of coolers running from a single Wall Controller
Each cooler can be set to run at dierent BMS Lock Speeds.
• The IEC and/or DEC input can be applied to any single cooler
in the group and all coolers will enter BMS Lock Mode.
ILL3936
30 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MULTI-MAGIC CONTROLS
TRI-COLOUR
LED
RED LED
ILL3686-A
ILL3686-A
OPERATION PHASE LED STATE
INITIAL BOOT UP.
FIRST 30-45 SECONDS AFTER
POWER UP
RED ON
TRI-COLOUR FLASHING GREEN
NORMAL RUNNING
RED ON
TRI-COLOUR ON AMBER
Note: Both PCBA LEDs are continuously ON once
communication between the PLC and PCBA has been
established.
WATER MANAGER LED STATES FAULT CODE DISPLAY
Active Fault Codes will cause
the FAULT button to appear on
the CONTROLS page.
Selecting the FAULT button
will open the ACTIVE FAULTS
page, listing all the current
active faults.
Select the INFO button to
display a QR code.
Scanning the QR Code will
direct users to the Seeley
Service Technical Support
website.
Select the RESET button to reset each active fault. Cycle the
cooler power to reset all active faults.
All faults are added to the FAULT CODE HISTORY screen.
On all screens, long press the LEFT button to return to the
CONTROL page.
ILL3653
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 31
FAULT CODE DESCRIPTIONS
MULTI-MAGIC CONTROLS
All faults below shut the cooler down unless stated.
Fault codes labelled as Running Faults will allow the cooler to continue to run, however performance may be reduced.
FAULT
CODE
FAULT DESCRIPTION SUGGESTED REMEDY
Fault Code 1 PLC – PCBA COMMUNICATION FAILURE
Cooler PLC has lost communication with PCBA tted inside
control box for at least 1 minute.
Check LED status on PCBA.
Check communication wiring between PLC and PCBA
Replace PCBA
Fault Code 2 FAILURE TO DETECT WATER AT LOW PROBE
No water at low probe 20 minutes after solenoid valve opening.
Check water supply on.
Check solenoid valve open.
Check drain valve closed.
Check water management probe position relative to drain valve overow.
Clean water management probe.
Fault Code 3 FAILURE TO DETECT WATER AT HIGH PROBE
No water at high probe 30 minutes after water detected at low
probe.
Check water supply on.
Check solenoid valve open.
Check water management probe position relative to drain valve overow.
Clean water management probe.
Check water supply pressure sucient to maintain tank capacity.
Fault Code 4 FAILURE TO CLEAR LOW PROBE DURING DRAIN
Water still detected at low probe 20 minutes after drain opened.
Check drain valve open.
Check drain pipework not blocked.
Check solenoid valve closed.
Clean water management probe.
Fault Code 5 WATER DETECTED AT HIGH PROBE BUT NOT LOW PROBE
Water still detected at high probe 30 minutes after water not
detected at low probe.
Clean water management probe.
Fault Code 7 SUPPLY MOTOR ERROR
Motor has been in fault state for at least 1 minute.
Check Motor Power Cable connections.
Check Motor Communications Cable connections.
Check MONITOR screen to identify which motor is in fault.
Fault Code 10 CHLORINATOR FAULT
Chlorinator has reached end of life or is experiencing a short
circuit. Running Fault
Check cooler PLC ashing LEDs for fault type.
Check no debris between chlorinator plates.
Replace Chlorinator
Fault Code 11 ROOM AIR SENSOR FAULT
Temperature or Relative Humidity input value has been 0V or
10V for at least 10 minutes. Running Fault
Check Sensor values at PLC cooler screen “SENSORS” menu
Check Sensor wiring
If no Sensor tted, check Sensor has not been accidentally enabled on Wall Controller
and/or PLC
Fault Code 12 AMBIENT AIR SENSOR FAULT
Temperature or Relative Humidity input value has been 0V or
10V for at least 10 minutes. Running Fault
Check Sensor values at PLC cooler screen “SENSORS” menu
Check Sensor wiring
If no Sensor tted, check Sensor has not been accidentally enabled on Wall Controller
and/or PLC
Fault Code 14 DUCT AIR SENSOR FAULT
Temperature or Relative Humidity input value has been 0V or
10V for at least 10 minutes. Running Fault
Check Sensor values at PLC cooler screen “SENSORS” menu
Check Sensor wiring
If no Sensor tted, check Sensor has not been accidentally enabled the PLC.
Fault Code 15 PRESSURE SENSOR FAULT
Pressure input value has been 0V or 10V for at least 10 minutes
whilst the fans fan been running. Running Fault.
Check Sensor values at PLC cooler screen “SENSORS” menu
Check Sensor wiring
If no Sensor tted, check Sensor has not been accidentally enabled the PLC.
Fault Code 16 COMMUNICATION FAILURE
PLC has lost communication with Wall Controller for at least 5
minutes.
Ensure cooler is powered up.
Check communication cable connections including 120Ω Modbus terminating
resistors.
32 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
COMMISSIONING
INSTALLATION CHECKLIST
This checklist only covers the key points to be observed during installation. Always refer to the relevant sections of the
installation manual for full details.
COOLER LOCATION
The cooler is adequately supported, secure and level.
The cooler is installed in a position that allows adequate access for future maintenance and servicing activities.
INTAKE AIR
The cooler will always receive a plentiful supply of fresh air.
□ Inlet air lters installed correct way round. Observe airow direction arrow on lter frame.
SUPPLY AIR DUCTWORK
□ Vibration absorbing exible connections are used for all duct connections to the cooler.
□ All building penetrations are correctly ashed and sealed.
□ If exible ducts are used, they are fully extended, hung correctly, with no kinks, tight bends, or squashed segments.
All duct joints are fully sealed with no air leaks.
EXHAUST AIR
The cooler’s exhaust air is not likely to cause corrosion or damage to other nearby items.
The cooler’s exhaust air is not likely to re-circulate into the air intake of the cooler.
□ Exhaust caps tted (CW-H15S PLUS only).
□ If exhaust air ductwork is tted, the static pressure drop does not exceed 20Pa (0.08 in wg).
ELECTRICAL SUPPLY
The electrical power supply installation adheres to all local and national regulations
The electrical power supply is wired back to the distribution board on its own separate circuit.
A mains isolation switch, with all pole disconnection, has been installed adjacent to the cooler.
□ The Line-Line Voltage (3~) or Line-Neutral (1~) is within the Rating Label specication.
440-480V coolers ONLY. Transformer tapping set to match mains voltage.
WATER SUPPLY
□ The water supply installation adheres to all local and national regulations with no leaks at any ttings or valves.
□ The water supply pipes were ushed of any foreign materials before connection to the cooler was made.
□ The water is ltered as required.
Static water pressure to each cooler is between 100kPa (15psi) and 800 kPa (115psi)
Opening and closing the inlet water solenoid valve does not cause water hammer.
□ Water ow rate to each cooler is greater than 10L/min (2.6 gal/min) when all coolers are lling.
Water salinity is greater than 100uS/cm.
An isolation valve has been installed adjacent to the cooler.
The owner has been instructed on how to isolate the water supply to the cooler in case of emergency.
WATER DRAIN
□ The water drain installation adheres to all local and national regulations with no leaks at any ttings or valves.
Drain water pipes/hoses are free from any restrictions (kinks) or blockages.
The drain water does not discharge onto the roof surface.
Commissioning Technician: ....................................................Signed by Installer: .................................................................
Owner Name: .............................................................................
Address: .....................................................................................
......................................................................................................
Dealer: ..............................................................
Date Installed: ..................................................
Telephone: ........................................................
Installer: ............................................................
Model No: .........................................................
Serial No: ..........................................................
Record the details
3~ Voltage L1-L2 .......................
3~ Voltage L1-L3 .......................
3~ Voltage L2-L3 .......................
1~ Voltage L-N ......................
Record the details
Water Pressure .......................
Water Salinity .......................
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 33
COMMISSIONING
WATER MANAGEMENT SYSTEM CHECKS
Turn inlet water solenoid valve ON.
□ Conrm water enters reservoir.
Wait until Tank Low Level (Tk Lo) probe changes state.
□ Conrm Water Salinity reading is greater than 100 uS/cm.
□ Conrm Chlorinator is fully submerged at low water level.
Wait until Tank High Level (Tk Hi) probe changes state.
Turn inlet water solenoid valve OFF.
HEAT EXCHANGER FLUSH
To reduce the probability of unusual odours, foaming or water
pull o, it is recommended to ush new heat exchangers with
fresh water and then drain the reservoir.
Turn Direct Pump (DRPump) ON (Supercool Coolers only).
□ Conrm Direct Pump starts.
□ Run for 5 minutes to ush the Direct Heat Exchangers.
Turn Direct Pump (DRPump) OFF.
Turn Indirect Pumps (IDPump) ON.
□ Conrm both Indirect Pumps start.
□ Run for 5 minutes to ush the Indirect Heat Exchangers.
Turn Indirect Pumps (IDPump) OFF.
Set Drain to OPEN.
□ Conrm the drain valve opens.
□ Conrm water fully drains from the reservoir.
SUPPLY FAN CHECKS
Set Supply Fan (SpFAN) to ON.
Set Speed initially to 1 and then progressively increase to 10.
Check for unusual or excessive sound output at various fan
speeds.
Check for excessive vibration and/or rattle sounds.
TEST MENU
ILL3887-A
To assist with commissioning, each component on the cooler
can be controlled individually via the SERVICE - TEST MENU
on the cooler PLC.
Set TEST to ON to control components.
Use the LEFT/RIGHT buttons to access 2 pages.
Record the details
Product Family. ..................................................
Model ..................................................
Voltage ..................................................
IMPORTANT: CW-H Supercool coolers are sold as one part
number, but can be congured in one of two ways, CW-H15S
or CW-H15S PLUS. Refer to the specifying consultants/
builders schedule of works or specication to conrm which
conguration is to be used.
Commissioning Technician: ....................................................Signed by Installer: .................................................................
SETUP MENU ACCESS
Push and hold the RIGHT
button until the password
screen is displayed.
Use the navigation LEFT/
RIGHT and UP/DOWN buttons
to enter password “7378” and
push OK to display the SETUP
screen.
MULTI-MAGIC DEVICE TYPE
Prior to running the cooler for the rst time, check the device
type in the PLC SETUP menu matches the cooler rating label.
ILL3678
TIME & DATE
To assist with fault code and drain history logs, set the time and
date in the PLC SETTING menu.
Use the navigation LEFT/RIGHT and UP/DOWN buttons to set
the Time, Date and Day.
Select SAVE to commit values to memory.
Note: If using BACnet, Time & Date are set by BACnet objects.
ILL3937
ILL3885-A
34 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
AIR FLOW BALANCING
In order for the cooler to produce cool air it is mandatory that
some of the inlet air is forced to return through the indirect heat
exchanger cores and be exhausted to atmosphere. Therefore
only a proportion of the total inlet air is delivered into the cooled
zone.
THIS PROPORTION IS CRITICAL TO ACHIEVING
SATISFACTORY PERFORMANCE.
The supply air transition is equipped with a damper that can
be adjusted to 'balance' the proportion of supply and exhaust
air streams. Damper position is controlled through a lever with
locking screw located underneath the supply air transition.
The damper will need to be adjusted during commissioning
depending on the external static pressure of the duct system.
ILL2447-A
ILL2447-A
To balance the air ow.
1. Ensure all side panels and air lters are in place.
2. Connect all external supply and exhaust ductwork.
a. Stand-alone Cooling: Fully open all supply air outlets
in the entire ductwork system.
b. Pre-Cooling: Ensure all main Air Conditioning plant
fans are running at full speed - consult with Building
Manager and/or Air Conditioning contractor.
3. Using the cooler's PLC, start the Climate Wizard in LOCAL
and IEC modes at Speed 10.
4. Wait approximately 5 minutes, to allow the cooler to
complete the rst water ll and the pumps to start.
5. Adjust the supply air transition damper until the pressure in
the transition stabilises as follows:
a. CW-H10: 200 Pa (0.80 in wg static)
b. CW-H15: 175 Pa (0.70 in wg static)
c. CW-H15S: 175 Pa (0.70 in wg static)
d. CW-H15S Plus: 210 Pa (0.84 in wg static)
6. For multiple CW-H coolers connected to the same supply
duct, it may be necessary to re-check and adjust the supply
air transition pressures of all coolers after each cooler is
set.
7. For stand-alone cooling, balance all customer’s supply air
outlets in your usual manner. After balancing, check and
adjust the CW-H damper back to the above values.
8. Lock the damper in its nal position and record the nal
value.
Supply Transition Pressure = ................................
ILL3884-A
There is a hole in the right hand side of the supply air transition
suitable for manometer tubes for measuring pressure.
NOTE! Pressure measuring should be carried out using
an accurate instrument, either electronic or “inclined tube
manometer”. DO NOT GUESS.
COMMISSIONING
Signed by Installer: .................................................................
Commissioning Technician: ...................................................
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 35
COMMISSIONING
Signed by Installer: .................................................................
Commissioning Technician: ...................................................
MULTI-MAGIC COOLER SETTINGS
To aid future servicing it is recommended to record the PLC
setting here.
SETTING VALUES
PRIMARY CONTROL METHOD
Local (LCL)
Wall Controller (W/C)
Low Voltage BMS (BMS)
High Level Modbus (MBS)
BACnet (BCN)
LANGUAGE
English (Default)
Spanish
Italian
French
Portuguese
PRE-WET
Enabled
Disabled (Default)
SALINITY DRAIN SET-POINT
4275 uS/cm (Default)
2305 uS/cm
BMS FAULT OUTPUT LOGIC
Normally Open (Default)
Normally Closed
SENSOR UNITS
Metric (Default)
Imperial
FAN START DELAY
0s (Default)
-120s
-90s
-60s
-30s
+30s
+60s
+90s
+120s
FAN RUN OUTPUT LOGIC
Normally Open (Default)
Normally Closed
BMS LOCK SPEED (0-10)
HIGH = _____
LOW = _____
MULTI-MAGIC RS-485 SETTINGS
If used, record the PLC settings for Wall Controller, Modbus and
BACnet MS/TP communication here.
SETTING VALUES
NAME*
Default = Cooler 1
Actual =
Unique NODE ADDRESS (1...99)
Default = 1
Actual =
BAUD RATE
9600
19200
38400 (Default)
57000
76800
115200
PARITY
NULL (Default)
ODD
EVEN
120Ω TERMINATING
RESISTORS
Wall Controller / Primary
Last Cooler
* Applicable to BACNet MS/TP only
CUSTOMER HANDOVER CHECKLIST
Run the cooler for at least 20 minutes in IEC and DEC mode at
Speed 10 and conrm,
□ Leaving temperatures are suciently cooler than ambient
temperatures.
No unusual odours.
No visible water leaks.
□ No excess water is draining from overow.
Finally, conrm that
All the installation rubbish has been removed.
Any property damage reported and/or repaired.
The customer has been given a copy of the cooler manual
which includes Operation, Maintenance & Warranty details.
MULTI-MAGIC IP SETTINGS
If used, record the PLC settings BACnet IP communication
here.
SETTING VALUES
IP ADDRESS
Default = 192.168.10.51
Actual =
GATEWAY
Default = 192.168.10.1
Actual =
SUBNET MASK
Default = 255.255.255.0
Actual =
BACNET IP PORT
Default = 47808 (0xBAC0)
Actual =
36 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
MAINTENANCE FREQUENCY
Maintenance of an indirect evaporative cooler is essential in maintaining proper performance and reliability.
All maintenance must be done by competent, qualied, licensed technicians, in accordance with National and/or Local Regulations.
The frequency of service is largely dependent on the conditions under which the cooler is operated. External factors, such as air and
water quality, can aect the serviceable life of the cooler and its components. In particular, installations using hard water, usually
dened as greater than 200mg/L, will experience greater scaling problems requiring a more frequent cleaning regime.
Similarly, the amount and type of use can also have a signicant impact. The guidelines listed below are intended to provide help in
formulating a proper service regime. Local, and in some cases, individual factors should be taken into account when deciding on the
frequency of visits.
HEALTH REGULATIONS. In some regions, regulations require that evaporative air coolers be serviced at specic intervals. Ensure
all maintenance is done in accordance with any local and national regulations.
TYPE OF INSTALLATION MAINTENANCE SCHEDULE
SERVICING FREQUENCY
AIR FILTERS CHLORINATOR
COMMERCIAL / INDUSTRIAL
INSTALLATIONS
(Seasonal use)
Maintenance Schedule servicing must
be a minimum of twice a year, typically
immediately before and after the
summer season.
Air lters should be cleaned every
month of operation and replaced every
year.
Chlorinators should be cleaned during
each service and replaced every 4
years.
COMMERCIAL / INDUSTRIAL
INSTALLATIONS
(All year use)
Maintenance Schedule servicing must
be performed every 3 months.
Air lters should be cleaned every
month and replaced every year.
Chlorinators must be cleaned during
each service and replaced every 2
years.
While installation is not covered by warranty (e.g. duct work, roof penetrations, electrical and water connections etc.), these items
should be checked as they can aect the performance (and/or safety) of the cooler. For this reason, they are included in the
Maintenance Schedule.
For access to Technical/Installation/Service Information register online at www.seeleyinternational.com/service
MAINTENANCE SCHEDULE
WINTER OPERATION AND SHUTDOWN
Climate Wizard coolers cannot be used in any cooling mode (INDIRECT, DIRECT or SUPERCOOL) in freezing conditions. In
particular the inlet water solenoid valve, pumps, and drain valve are likely to fail in such conditions.
It is recommended that, to prevent damage to cooler components, the following tasks are completed before the start of the winter
season.
1. Drain and clean the reservoir.
2. Drain down and isolate the water supply.
3. Isolate the power.
For installations requiring continuous operation through the winter, it is possible to run the cooler in VENT mode down to -20
o
C
(-4
o
F), however customers must ensure the controls are not accidently set to any cooling mode in these conditions.
Coolers tted a Multi-Magic Ambient Sensor will automatically enable freeze protection. See page 27 for full details.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 37
MAINTENANCE CHECKLIST
DEFINITIONS
Clean - To wash and remove all dirt, grit or debris.
Check/Inspect - To visually inspect the item for correct operation, tment and functionality.
Test - To turn the item on and o and conrm correct function.
Replace - To remove the existing item and replace with a specied genuine replacement part.
Note! It is important that only new Seeley International factory authorised replacement parts be used in this cooler. Failure to do so
may void warranty, cause improper cooler performance, and unsafe operation.
SERVICE NO. 1 2 3 4 5 6 7 8 9 10 11 12
EXTERNAL INSPECTION
Check/Inspect the following parts for general deterioration, leaks, damage, corrosion, missing components, secure connections, and function.
Cooler Body
Supply Air Duct
Support Frames / Curb
Vibration Isolation
Roof Flashing
Isolation Switch
Circuit Breakers/Fuses
Power Cables
Communication Cables
Water Supply Pipe
Water Supply Strainer/Filter
Water Isolation Valve
Drain Hose
Remove & Clean the following components.
Air Filters*
MAINTENANCE SCHEDULE
INTERNAL WATER DISTRIBUTION
Check/Inspect the following for general condition, damage and secure connections.
Water Distribution Hoses
Remove & Clean the following components
Pump Strainers
Water Probe Pins
Chlorinator Cell*
Tank Surfaces
Test the following components
Water Probe Resistance
HEAT EXCHANGERS
Remove & Clean the following components
Indirect Spreaders
FAN & MOTORS
Check/Inspect the following for general condition and damage.
Supply Fan Blades
Supply Motor Mounts
Test the following.
Supply Motor Spins Freely
* Air Filters and Chlorinators require replacement based on usage. Refer to frequency of service guidelines.
38 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
SERVICE NO. 1 2 3 4 5 6 7 8 9 10 11 12
FUNCTIONAL TEST
Test the following components service screen.
Inlet Solenoid Valve
3-Pin Water Probe
Drain Valve
Indirect Pump
Direct Pump
Supply Fan Speed Control
Check/Inspect the following whilst running at full speed.
No excessive noise
No excessive vibration
No water leaks
Correct internal water levels
MAINTENANCE SCHEDULE
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 39
MAINTENANCE INSTRUCTIONS
REAR VIEW
SIDE VIEW - LHS
ILL1954
Water Inlet Solenoid
Chlorinator
Pumps
Cores
Water Distribution Spreaders
Reservoir access
Pump
Access
Panel
Core
Access
Panel
SIDE VIEW - RHS
Water Management Probe
Drain Valve
Pumps
Pump
Access
Panel
Core
Access
Panel
Cores
Water Distribution Spreaders
Reservoir access
ILL2448
ILL3683
QUARTERLY INSPECTION PROCEDURES
1. Drain the cooler reservoir by initiating a manual drain
2. Isolate and lockout the power supply to the cooler.
3. Turn o the water supply.
4. Remove the service access panels from both sides of the
cooler.
5. Clean the Pump Strainers & Impellers.
6. Clean the Chlorinator Blades.
7. Clean the Water Management Probe.
8. Clean the Water Reservoir.
9. Clean or Replace the Inlet Air Filters.
10. Inspect the entirety of the cooler body and external
components for general deterioration, leaks, damage,
corrosion, and loose or missing fasteners.
11. Re-t the service access panel to both sides of the cooler.
Apply a liberal coat of anti-seize paste to the screw
threads prior to tment.
12. Turn on the power and water supply.
13. Complete the cooler commissioning sequence.
COOLER CONTROL
Liaise with the Building Manager prior to starting a service.
To avoid any unintended cooler operation from commands
received by remote controller, it is recommended that the cooler
is set to LOCAL control before performing any maintenance.
ILL3682
To assist with maintenance and fault nding, each component of
the cooler can be controlled individually via the TEST MENU on
the cooler PLC.
IMPORTANT: UPON COMPLETION OF SERVICE ENSURE
PLC CONTROL IS SET BACK TO ORIGINAL SETTING (WALL
CONTROLLER, MODBUS, BMS, OR BACNET)
ILL3913
Push and hold the RIGHT
button until the password
screen is displayed.
Use the LEFT/RIGHT and
UP/DOWN buttons to enter
password “7378” and push
OK to display the SETUP
screen.
Use the UP/DOWN buttons
to move the cursor to
SERVICE and push OK.
Use the UP/DOWN buttons
to move the cursor to TEST
MENU and push OK.
Set TEST = ON
Use the UP/DOWN buttons
to move the cursor between
component and push OK to
change state.
Push and hold the LEFT
button to return to the
previous menu. Repeat
until the display returns to
the “CONTROL” menu.
Use the LEFT/RIGHT
buttons to switch between
dierent Test Menu
screens.
40 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WATER INLET SOLENOID VALVE
SOLENOID VALVE MAINTENANCE
No regular maintenance of the solenoid valve is required.
ILL1954
Pump
Access
Panel
SOLENOID VALVE REPLACEMENT
1. Turn o the water supply.
2. Remove the breather hose from and unclip the solenoid
cover (B).
3. Remove the outlet hose from the bottom of the solenoid
valve.
4. Undo and remove the water inlet nipple (D) from the old
solenoid.
5. Fit the new solenoid to the bracket (C) with a new water
inlet nipple (D) and o-rings (E) and (F).
6. Unplug the old solenoid lead from the main PCBA, (refer
to the wiring diagram on the control box door for the plug
point location), remove the lead from the cable gland at the
base of the control box and pull through the rubber gland
mounted below the control box. Use the old cable to pull
the new cable to the opposite side of the cooler. Plug the
new solenoid into the PCBA.
7. Re-attach the outlet hose, ensuring there is a 10mm (3/8")
gap between the top of the hose and the top of the slot in
the solenoid - this is to prevent a vacuum being created
(refer diagram below).
8. Re-t the breather hose and solenoid cover (B).
G
FED
C
B
A
A SOLENOID VALVE, NYMET BRAND, 12VDC, 1000KPA
B SOLENOID COVER
C SOLENOID COVER BRACKET
D FITTING1/2" BSP
E O’RING 19MM ID
F O’RING 25MM ID
G RIVET 1/8" (X4)
H BLANKING GROMMET 12MM (NOT SHOWN)
I PRESSURE HOSE 300MM (NOT SHOWN)
19mm
25mm
O’RING ORIENTATION
OUTLET HOSE
10MM GAP
ILL2454-A
ILL2454-A
Water Inlet Solenoid
Chlorinator
Pumps
Cores
Water Distribution Spreaders
Reservoir access
Core
Access
Panel
ILL1956-A
MAINTENANCE INSTRUCTIONS
PUMP REPLACEMENT
Pumps are wired in parallel via a junction box located below the
cooler lid back panel.
Trace the pump cable back to the pump junction box to identify
the correct cable gland and terminal junctions.
Replicate the pump basket orientation with the pump being
removed.
Unscrew the 2 screws securing the pump to the bracket and
ret to the new pump.
INDIRECT & DIRECT PUMPS
Quantities and locations of pumps for each model are shown
below.
ILL2450
CW-H10 = 1,
CW-H15 = 1,
CW-H15S = 1,
CW-H15S Plus = 1
CW-H10 = 1
CW-H15 = 1
CW-H15S = 2
CW-H15S Plus = 2
PUMP
JUNCTION BOX
(UNDER LID)
PUMP MAINTENANCE
Cleaning Pump Strainers & Impellers
1. Cut the cable tie securing the pump leads and remove the 2
screws securing the pump bracket to the wall of the cooler.
2. Disconnect the plumbing hose from the spigot at the pump
base.
3. Remove the pump assembly from the cooler cabinet.
4. To remove pump from the strainer, press the release button
on the strainer, twist the pump body clock-wise with button
depressed and lift the pump body out of the strainer base.
Note the orientation prior to removal.
5. Inspect and clean the pump strainer and impellor housing.
Remove any solids or residues from the strainer slots or
around the impellor with a soft brush.
6. Re-assemble in the reverse order, use a new cable tie to tidy
and secure all the cables again.
Note! When removing or unplugging pumps, take care to ensure
they are replaced correctly.
The pump body must be seated ush in outlet housing
otherwise it will not pump sucient water.
• Check the integrity of the hoses and their connection to the
pump spigots.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 41
CHLORINATOR MAINTENANCE
The chlorinator is tted to a bracket located underneath the
water inlet solenoid valve. The chlorinator and bracket can
be removed together. To remove, detach the water hose and
unscrew the bracket from the cooler body.
It is normal for the chlorinator cell blades to be covered in white
deposits.
1. Remove any excess solids gently, using a soft brush, prior
to immersion
2. Wash or hose the chlorinator cell in clean water (hot water
if possible).
3. Immerse the chlorinator cell in a plastic container with 5%
phosphoric acid solution for at least 10 minutes. Be sure
to clean the inner surfaces of the chlorinator cell blades
4. Rinse with fresh water & reassemble chlorinator. Ensure
chlorinator spacing clip is in place.
IMPORTANT - ENSURE THE CHLORINATOR AND 4-WAY
DISTRIBUTOR SIT PARALLEL TO THE BRACKET AS
SHOWN.
CHLORINATOR
CHLORINATOR REPLACEMENT
Unplug the chlorinator lead from the main PCBA, (refer to
the wiring diagram on the control box door for the plug point
location), remove the cable from the cable gland at the base
of the control box and pull through the rubber gland mounted
below the control box. Use the old cable to pull the new cable to
the opposite side of the cooler.
ILL2451-A
ILL2451-A
WATER MANAGEMENT PROBE
WATER MANAGEMENT PROBE MAINTENANCE
1. Open the pump access panel. Cut the cable tie securing
the probe lead to the pump hose.
2. Unclip the probe from the bracket, pull the lead through
the opening in the bracket and pull the probe out from the
enclosure (there is sucient lead length to clear the pump
enclosure). Remove the small plastic shrouds from the rst
and third pins.
3. Clean the pins by wiping the contact surfaces with a soft
cloth - do NOT use abrasives.
4. Check the probe pin resistances using a multi-meter (refer
gure and wiring diagram - you’ll need to unplug the probe
lead from the main PCB to do this).
Resistance should be 0-5 ohms. A reading of 5 ohms or greater
indicates a faulty probe. Check for shorts between pins: There
should be an open circuit.
5. Ret the shrouds over pins 1 & 3. Ret the probe to the
bracket, making sure the clip is fully engaged and square
(the clip makes a “click” sound when properly engaged).
WATER MANAGEMENT PROBE REPLACEMENT
1. Unclip the probe from the mounting bracket, unplug the
probe lead from the main PCB, remove the lead from the
cable gland at the base of the control box, pull the lead
through the rubber gland mounted below the control box
from the access panel opening.
2. Ret the assembly. Use a new cable tie to tidy and secure
all the cables again and re-assemble.
Pin 1
Pin 2
Pin 3
0.00
+
-
PIN1(BLUE)
PIN2(BLACK)
PIN3(BROWN)
PIN4(EMPTY)
Pinshrouds
shownin dotted
line for clarity
Clean the water levelprobes by wiping
the contactsurfaces withasoft cloth.
ILL2452-A
ILL2452-A
SIDE VIEW - LHS
ILL1954
Water Inlet Solenoid
Chlorinator
Pumps
Access
Panel
SIDE VIEW - RHS
Water Management Probe
Drain Valve
Pumps
Access
Panel
ILL2448
MAINTENANCE INSTRUCTIONS
42 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
INLET AIR FILTERS
The inlet air lters should be replaced as soon as the airow
through the lters is restricted by dust or contaminants. The
frequency of changing the inlet air lters is dependent on the air
quality at the site.
Replacement inlet air lters are available from SI Service
Agents and Climate Wizard Distributors. If alternative air lters
are supplied, they should be to EN779 G4 or ASHRAE 52.2
MERV8 standards as a minimum.
To access the Inlet Air Filters, the centre front panel of the Air
Filter Cowling must be removed by releasing x4 quarter-turn
fasteners.
ILL3619-A
ILL3619-A
The Inlet Air Filters slide in and out of the Air Filter Frame.
When tting, use the air ow direction sticker on the side of the
lter to ensure the correct orientation.
Ensure the 2x retaining brackets are re-tted.
QUARTER TURN LOCKS IN
ALL 4 CORNERS OF THE
DOOR PANEL
Lift and slide out the 2x retaining brackets holding the lters in
place.
ILL3620-A
OTHER BRACKET
OBSCURED IN THIS
VIEW
ILL3620-A
DRAIN VALVE
DRAIN VALVE MAINTENANCE
No regular maintenance of the drain valve is required; however
it is sometimes necessary to remove the drain valve fully during
tank ushing.
DRAIN VALVE REPLACEMENT
1. Unplug the drain valve lead from the main PCBA, (refer
to the wiring diagram on the control box door for the plug
point location), remove the lead from the cable gland at the
base of the control box and pull through the rubber gland
mounted below the control box.
2. Remove any drain ttings from the bottom of the Drain
Valve.
3. Undo the drain valve nut on the bottom of the reservoir and
lift the drain valve out of the cooler.
4. Before replacing, ensure the sealing surface of the
reservoir and the o-ring is free of any derbis. This is
important to prevent leaks.
5. Make sure that the O-Ring (2) and Retainer (3) is tted to
the drain valve thread before replacing the valve back into
the reservoir. Screw the nut (4) up tightly by hand through
the drain valve access panel. Do not overtighten the nut.
6. Re-t the drain ttings to the bottom of the Drain Valve.
7. Run the new drain valve cable through to the control box
and connect to the PCBA.
ILL2453-C
2
1
5
4
6
3
NUT ORING/
TANK FLOOR
ELBOW
ADAPTOR
DRAIN VALVE
ACCESS PANEL
1. = DRAIN VALVE ASSY
2. = O RING (Inside)
3. =RETAINER (Inside)
4. = NUT (Outside)
5. = DRAIN ELBOW (Outside)
6. = FLEXIBLE DRAIN ADAPTOR (Outside)
ILL2453-C
MAINTENANCE INSTRUCTIONS
SIDE VIEW - RHS
Water Management Probe
Drain Valve
Pumps
Access
Panel
ILL2448-A
Slide up to
remove
WATER RESERVOIR (TANK)
Flushing of the water reservoir is best achieved with the
pumps/chlorinator and water management probe removed.
In instances of large amounts of solid debris, it is also
recommended to remove the drain valve.
Use a water hose or low-pressure cleaner to ush all debris
down the reservoir drain. After ushing wipe the bottom of the
reservoir thoroughly using a wet cloth or brush.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 43
ILL2450
CORE AND SPREADER
ASSEMBLIES (LID REMOVED)
4. Open the core access panels on either side of the cooler.
5. Remove the metal core clamp strips
6. Disconnect the spreader assembly from the rubber core
extrusions and remove the water spreader assemblies.
They can be placed aside onto the lid of the cooler cabinet
while still remaining connected to the plumbing system.
TOP VIEW
LAY THE WATER SPREADER TRAYS
(TEMPORARILY) FROM THE TOPS
OF THE CORES BACK ABOVE THE
FAN HOUSING.
ILL2456-A
ILL2456-A
1. Power OFF, water OFF.
2. Disconnect and remove any xed ducting from the exhaust
outlet of the cooler (if tted).
3. Remove the exhaust transition/lid assembly from the
cooler.
INTERCHANGE CORES THROUGH THE
ACCESS PANEL OPENING.(BOTH SIDES)
ILL2462-A
ILL2462-A
MAINTENANCE INSTRUCTIONS
7. The cores can now be slid out from either side of the cooler
through the access panel openings. Take care to ensure
the cores are not damaged during removal. They can be
heavy and fragile when wet. Grasp the cores around the
top section to ensure no delamination of the core occurs
while moving them.
Grasp the cores around the top
sectionwhilstmoving them.
ILL2457-A
ILL2457-A
8. To re-assemble, position the cores into the cooler starting
at the centre. For all cores the front of the core must face
the cooled air outlet of the cooler as below.
PATTERN
CHANGES
FRONT
TOP VIEW
PATTERN
CHANGES
FRONT
RUBBER SEAL
EXTRUSION
Changing Cooler Cores-Orientation
Side View
TopView
REAR
REAR
FRONT
FRONT
ILL2458-A
ILL2458-A
INDIRECT HEAT EXCHANGERS
The indirect heat exchanger cores do not require any
maintenance other than visual inspection, which can be
completed without removal from the cooler.
However it is recommended that, after 7 years of operation
and for each subsequent year of operation, all indirect heat
exchangers are removed for a detailed inspection.
During a full inspection, check the following areas.
• Air intake face and dry channels are clear of dirt, debris and
calcium build up.
• Glue seams are fully sealed, with no splits greater than 10cm.
• Wet channel air-entry slots are not bridged by calcium build
up.
LAY THE WATER SPREADER TRAYS
(TEMPORARILY) FROM THE TOPS
OF THE CORES BACK ABOVE THE
FAN HOUSING.
ILL2456-A
44 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
DIRECT HEAT EXCHANGERS (CHILLCEL)
(CW-H15S, H15S Plus ONLY)
1. Remove the lid / exhaust assembly.
2. Remove the indirect heat exchangers to expose the
3 Chillcel pads located in the cooler supply air outlet
transition.
3. Remove the Chillcel cover plate.
4. Slide the Chillcell out from underneath the water spreader
assembly.
5. To re-assemble, rst note the Chillcel has a small header
block; this is the top of the pad and must be positioned
under the water spreader for the pad to function correctly.
6. Ensure the re-tted Chillcel sits upright against the water
spreaders and tightly against each other.
ILL3939
9. Locate the water spreader assembly front ange into the
extrusion at top front of the cores.
10. Check the cores t snugly and squarely across the width of
the core platform and are rmly butted together. Check for
a uniform gap at either side of the cooler between the side
walls and the core. The core access door has a seal to take
up any resultant gap.
Locate the flange of the spreader housing into
the recess of the extrusion at the rear of the core.
ILL2459-A
ILL2459-A
11. Ensure a good seal between the cores and the access door
when closing. When re-securing the access doors, start
from the bottom screws and work up.
12. Ret the core clamp strips clamping over the extrusion
located at the top of the cores.
Checkthe cores are butted together
with no gaps between them.
ILL2460-A
ILL2460-A
13. Ret the exhaust transition/lid assembly to the cooler.
14. Ret any xed ducting to the exhaust outlet of the cooler.
15. Turn water and power back on to the cooler.
CORE CLAMP STRIP BEFORE
REMOVAL. NOTE THE RUBBER
EXTRUSION IS FULLY INSERTED
UNDER THE CLAMP STRIP.
ILL2461-A
ILL2461-A
MAINTENANCE INSTRUCTIONS
ELECTRICAL ENCLOSURE
The cooler electrical controls enclosure is manufactured from
steel coated in a thermosetting epoxy polyester powder paint.
Care should be taken to avoid causing deep scratches, dents
or cleaning using an abrasive brush. Wipe clean with sponges
and clean water.
Any local areas of corrosion or cracked paint can be treated
by applying a heavy duty, zinc-rich, anti-corrosive coating,
often called “Zinc Rich Primer” or “Cold Galv”. First ensure
the surface is free from dust, dirt, grease, oil, rust, scale and
other contaminants and then follow the coating manufacturer’s
application instructions.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 45
TROUBLESHOOTING
MAINTENANCE INSTRUCTIONS
PROBLEM POSSIBLE CAUSE SUGGESTED REMEDY
Cooler fails to start/
not running.
Cooler in fault.
Clear active faults.
Check wall controller fault code log.
Check tri-colour LED for fault code.
No power to cooler.
Check circuit breaker.
Consult with building manager.
Wall control in 7-day program mode.
Adjust setpoint and/or timer settings.
Switch to manual mode to check fan operation.
Cooler not receiving commands.
Set to PLC control method to W/C, MBS or BMS as required, see Multi-Magic
Control Schemes.
Inadequate cooling.
Cooler running in vent mode. Turn to cool mode.
Incorrect wall control temperature setpoint.
Adjust wall control setpoint.
Move wall control to more appropriate location.
DEC stage not operating (Supercool coolers only.)
Check controller humidity setpoint is not too high.
Check cooler device type is set correctly (CW-H15S or CW-H15S Plus)
Plenum pressures too low. See Commissioning section for Air Flow Balancing
Clogged or dirty inlet air lters Clean or replace air lters.
Clogged or dirty heat exchanger cores. Clean or replace cores.
Water pump failure. Check all pumps are operating.
Pumps run but insucient water in tank.
Clean or replace water probe.
Check water management probe position relative to drain valve overow
Check cooler is level.
Pumps run but no water circulation or heat exchanger cores
lack water
Clean pump strainer.
Check water distribution system for possible obstruction in hoses.
Check for blockages in the spreaders feeding the core assemblies.
Inadequate exhaust from building.
Make sure there is adequate provision for exhausting air from building (open
windows and doors).
Under-sized ducts.
Carry out cooling load design to determine correct size unit, ducting and
outlets required. Discuss with building manager.
Under-sized cooler.
High ambient humidity.
On days during summer when ambient humidity is high the cooler will not
reduce the temperature as much as on drier days. There is no remedy.
Excessive humidity.
Inadequate exhaust from building.
Make sure there is adequate provision for exhausting air from building (open
windows and doors).
Reduce DEC usage (Supercool coolers only.)
Discuss with building manager
Adjust controls program.
Noisy cooler.
Fan out of balance due to dirt, etc. Clean the fan.
Air duct noise Increase size of ducts. Increase size of room registers/grilles
Unpleasant odour.
New heat exchanger cores. See Commissioning Section for Cooling Core Flush
Cooler located near source of unpleasant odour. Remove source of odour or relocate cooler.
Algae in reservoir water. Drain reservoir, clean thoroughly with strong cleansing agent, rell.
Cores remain wet after shutdown.
Run cooler on VENT mode after cooling cycle to dry heat exchanger cores
out.
External water leaks.
Loose water hose connections. Check and tighten connections.
Blocked or undersized drains. Check and clean drain lines.
Excessive amounts of water from drain hose.
Check drain valve seal.
Check water management probe position relative to drain valve overow.
Check cooler is level.
Water carryover in
supply airstream.
Clogged or dirty heat exchanger cores. Clean or replace cores.
New heat exchanger cores. See Commissioning section for Cooling Core Flush
Heat exchanger cores not tted correctly into plenum. Check for air gaps around water spreaders and between cores.
Water carryover in
exhaust airstream.
Plenum pressures too high See Commissioning section for Air Flow Balancing
External static pressure too high. Increase size of ducts. Increase size of room registers/grilles.
Core seals/spreaders moved during transport.
Check spreader assemblies securely clamped to top of cores and gaps
between cores covered up.
Check core doors correctly sealing against sides of cores.
46 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WARRANTY TERMS (AUSTRALIA)
HOW TO REGISTER YOUR PRODUCT WARRANTY (Australia only)
Please register your warranty online by visiting seeleyinternational.com
Step 1 - select “Support” then “Register for Warranty”
Step 2 Enter your product serial number and “Submit”
Step 3 Enter the required information and “Submit”
Important Note: You need to have the following information to complete your registration:
your unit model and size
serial number
date your system was installed
name of the dealer you purchased it from
Please complete this section. You will also need to retain your purchase receipt, and proof of any warranty period extension.
Brand: _________________________________________________________
Model: _________________________________________________________
Serial No: _________________________________________________________
Customer Name: _________________________________________________________
Installation Address:_________________________________________________________
Installation Type: Residential / Non Residential / Commercial
Date of installation: _________________________________________________________
Installer / Dealer: _________________________________________________________
As with any product that has moving parts or is subject to wear and tear, it is VERY IMPORTANT that you maintain your Cooler and
have it regularly serviced. It is a condition of warranty cover for your Cooler that you comply with all of the maintenance and service
requirements set out in the Owner’s / Operation / Service Manual. Compliance with these requirements will prolong the life of your
Cooler. Further, it is also a condition of warranty cover that each item in the Maintenance Schedule in the Owner’s / Operation /
Service Manual is performed with the frequency indicated, by a qualied, licensed technician, and that the Maintenance Schedule is
properly lled out (i.e. names, signature, date, and action taken) when the item is completed.
ANY FAILURE TO CARRY OUT THE REQUIRED MAINTENANCE AND SERVICING REQUIREMENTS, AND ANY FAILURE TO
PROPERLY FILL OUT THE MAINTENANCE SCHEDULE, WILL VOID YOUR WARRANTY.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 47
WARRANTY TERMS (AUSTRALIA)
In this warranty:
We or us means Seeley International Pty Ltd (Seeley) ABN 23 054 687 035, and our contact details are set out at the end of this
warranty;
You means you, the original end-user purchaser of the Goods;
Supplier means the authorised distributor or retailer of the Goods that sold you the Goods in Australia;
Goods means the product, unit, appliance or equipment which was accompanied by this warranty and purchased in Australia; and
Relevant Warranty Period means the various warranty periods as described in clause 1 and clause 3 below, as appropriate.
Our Goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or
refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have
the Goods repaired or replaced if the Goods fail to be of acceptable quality and the failure does not amount to a major failure.
In addition to any rights and remedies that You may have under the Australian Consumer Law or any other law, subject to the terms
of this warranty, We provide the following warranty:
1. If during the rst one (1) years from the date of purchase, the Goods upon examination prove defective by reason of improper
workmanship or material, We will repair or replace, at our option, the Goods or any part thereof without charge for either parts or
labour, during normal working hours.
2. The warranty granted under clause 1 applies to all components which form part of the original cooler, but does not cover:
a) fair or normal wear and tear;
b) damage, loss or claims caused by, resulting from, or arising out of any utilities that service or are connected to the Goods.
This includes but it is not limited to electrical surges, and inadequacies, failure, or other problems in or with any electricity,
power, or water supply to the Goods;
c) after the rst year: (i) the replacement, supply, or servicing of consumable items (including without limitation cooler pads,
washers, seals, drive belts) and (ii) maintenance adjustments to the cooler; and
d) despite clause 2.c. above, air lters;
e) installation (including without limitation ductwork, ttings, and other related installation components) which is excluded.
f) batteries (including damage caused by leaking or faulty batteries), cracking or breaking of display screens in controllers,
physical damage caused by the user or third parties, and accidental breakage.
3. Seeley also warrants the Fan Motor for the rst three (3) years from the date of the Goods purchase, if upon examination prove
defective by reason of improper workmanship or material, We will repair or replace at our option, the Fan Motor or any part
thereof without charge for parts, during normal working hours.
4. During the period to which any expressed warranty applies, all defective part(s) shall be replaced or repaired (at the discretion
of Seeley) without charge for either parts or labour, during normal working hours. Should we deem in our absolute discretion
to replace the Goods pursuant to clause 1 or clause 3, we may substitute any similar good even if it is not on our current price/
equipment list. Further, Goods presented for repair may be replaced by refurbished goods of the same type rather than being
repaired. Refurbished parts may be used to repair the Goods.
5. We are under no obligation to repair or replace the Goods or Parts under clause 1 and 3 above if (i) the Goods have not been
installed and commissioned in accordance with the Installation Manual (ii) the Goods have not been installed and commissioned
properly or competently, (iii) the Goods have not been operated, serviced and maintained in accordance with the instructions
provided in the Owner’s Manual, or (iv) if any such service or maintenance has not been properly or competently performed. It
is a condition of warranty cover that each item in the Maintenance Schedule in the Owner’s / Operation / Service Manual (if it
was published with such a Schedule) is performed with the frequency indicated, by a qualied, licensed technician, and that the
Maintenance Schedule is properly lled out (ie names, signature, date, and action taken) when the item is completed. Any failure
to carry out the required maintenance and servicing requirements, and any failure to properly ll out a Maintenance Schedule
in the Manual, will void your warranty. The addition of any third party device, (except where it is required by the installation
instructions and complies with those instructions), or the removal or alteration of any Seeley component, or damage due to
misuse of the unit, or faulty installation or commissioning, will void this warranty.
6. As far as the law permits, We will not be liable for any consequential loss suered through, or resulting from, the non-operation,
or ineective operation of the cooler. The warranties granted under clause 1 and clause 3 do not cover damage to the cooler or
other loss resulting from acts of God.
7. No other person, company or corporation is authorised to oer, or give on our behalf, any other warranty. The benets conferred
are in favour of You and any person deriving title to the cooler whilst in its original place of installation. Nothing in this warranty
shall be construed as aecting any rights You may have under all the relevant laws, or Commonwealth or State Legislation which
give You rights which cannot be modied or excluded by agreement.
8. In order to claim under the warranties granted under clause 1 or clause 3 You must:
a) either:
contact us within the Relevant Warranty Period on Australia 1300 650 644; or
log a warranty claim on our website (website address below) within the Relevant Warranty Period; and
b) make available for inspection by the service agent who will come to the location of the Goods or send to us at the address
below within the Relevant Warranty Period: (i) the legible and unmodied original proof of purchase, which clearly indicates
the name and address of the original retailer, the date and place of purchase, the product name or other product serial
number, (ii) all of your records of all service and maintenance carried out to the Goods, plus the Maintenance Schedule in the
Owner’s Manual (if it was published with such a Schedule), (iii) a copy of the completed Warranty Information section above,
and (iv) if an extended warranty period was provided by Seeley International for the Goods, then the relevant document
provided by Seeley International conrming that extended warranty period. If you choose to send the documents described
in (i) to (iv) to Seeley International, then they must be accompanied by a covering letter which states your name and address
and daytime telephone number, the address at which the Goods are installed, and the model and serial number of the
Goods.
48 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WARRANTY TERMS (AUSTRALIA)
9. The warranty granted in clause 1 and clause 3 covers the costs of parts and labour but you will be responsible for:
a) the cost of travel incurred for a Seeley International service agent to get to and from the location of the Goods if the
location of the Goods is either: (i) outside the metropolitan areas of the capital cities; or (ii) more than 35 kilometres from an
authorised Seeley International branch or service representative; and
b) any costs for additional labour or equipment associated with gaining acceptable and safe service access to the Goods
installed in restricted, high or unsafe locations, and/ or the removal and replacement of any barrier, walls, roofs, fences etc;
and
c) any costs incurred by the Seeley International service agent in gaining access to the Goods which is necessary to comply
with any safety or workplace safety requirements and/or any other relevant regulations. For the avoidance of doubt, the
reference to any costs incurred also includes the cost of any necessary site inductions.
10. We are not responsible in any way for any failure and/or inadequate performance of the Goods which arises from or is connected
to the use in the Goods of non-genuine spare parts. Seeley International strongly recommends that only spare parts supplied or
approved by it are used in the Goods.
11. The employees and Executive of Seeley International are not responsible for the installation of the Goods and expressly disclaim
all liability resulting from incorrect installations or installations that do not conform to local electrical codes, local plumbing codes,
Occupational Health and Safety requirements, and by laws which are legislated or in eect at the time of installation.
12. This warranty is only valid and enforceable in Australia.
Note: It is important that the safety and privacy of our service technicians is protected at all times. Accordingly, We and our Seeley
International service agents reserve the right to refuse service if (i) safety and accessibility to the unit cannot be guaranteed or
(ii) the owner of the unit, occupant of the site where the Goods are located, or any other third party seeks to take photographs, or
make a video or audio recording, of the service technician(s) while they are on the site or carrying out service to the unit. If a service
technician attends the site but subsequently leaves for any of these reasons then a service charge will be made for the call which
charge shall be a debt immediately due and payable by the person or entity that has made the claim under this Warranty. If a service
call reveals no warranty fault found with the Goods, a charge will be made for the call.
Our liability under this warranty is limited to the extent permitted by law. That is, to the extent that it is fair and reasonable, if the
Goods are not of a kind ordinarily acquired for personal, domestic or household use or consumption, your remedies associated with
any failure or defect of the Product will be limited to:
a) the replacement of the Goods or the supply of equivalent goods;
b) the repair of the Goods;
c) the payment of the cost of replacing the Goods or of acquiring equivalent goods; or
d) the payment of the cost of having the Goods repaired
and subject to the terms and conditions included in this warranty.
SERVICE DEPARTMENT
Seeley International Pty Ltd
112 O’Sullivan Beach Road
Lonsdale, South Australia 5160
Customer Service Centre 08 8328 3844
Website: www.seeleyinternational.com
FOR SERVICE
To book a Service on your Seeley International product:
Visit www.seeleyinternational.com the select “Support” and “Find Agent / Book Service” then enter the required information.
or Phone Australia 1300 650 644 to be directed to your closest authorised Service Agent.
PRIVACY NOTICE
Seeley International Pty Ltd ABN 23 054 687 035 will use the personal information you provide us with to provide warranty support for the product you have purchased
and to inform you about other products and services. If you choose not to supply us with the information requested, we may be unable to provide you with warranty
support. We may also disclose your information to third parties, such as related entities; retailers, distributors, service agents and contractors who are aliated with us;
or marketing or market research companies. If you would prefer not to receive direct marketing communications from us, please follow the instructions to “unsubscribe”
which will be included in the direct marketing communications we send you, or contact our Privacy Ocer using the details set out below. While we do not currently
transfer personal information to overseas recipients or store personal information overseas, if we transfer your information to third parties who do so, we will take
reasonable steps to ensure that the overseas recipients do not breach the Australian Privacy Principles. By registering your warranty, you consent to having your personal
information used in this way. Please read our Privacy Policy on our website www.seeleyinternational.com for further explanation of how we collect, use, hold and disclose
personal information, and how you may access and seek correction of your information. It also sets out how you may complain about a breach of the Australian Privacy
Principles, and how we will deal with your complaint. You may contact us at: Privacy Ocer, Seeley International Pty Ltd, 112 O’Sullivan Beach Road, Lonsdale, South
Australia 5160.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 49
50 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WARRANTY TERMS (USA)
In this warranty:
We or Us means Convair Cooler Corporation doing business as Seeley International Americas (“SIA”), and our contact details are
set out at the end of this warranty;
You and Purchaser means the original end-user purchaser of the Goods;
Supplier means the authorized distributor or retailer which sold you the Goods;
Goods means the CW3, CW-H, or CW80 model of the Climate Wizard cooler which was accompanied by this warranty and is
intended for industrial and commercial use and not for personal, residential, or household use. There is no warranty on the Goods
for personal, residential, or household use; and
Relevant Warranty Period means the warranty period described in “Express Limited Warranty” below.
Do not use cooler cleaners, cooler treatment, or other additives to your cooler. The use of any of these products will void your
warranty and may impair the performance of your cooler.
ELIGIBILITY: THE COOLER MUST BE REGISTERED WITHIN 45 DAYS OF INSTALLATION AT:
www.seeleyinternational.com/americaswarranty
SIA SHALL HAVE NO LIABILITY RELATED TO THE CLIMATE WIZARD COOLER OTHER THAN FOR BREACH OF THE
EXPRESS WARRANTY STATED HEREIN, AND YOU RELEASE AND DISCHARGE US FROM ALL OTHER CLAIMS,
WHETHER IN CONTRACT OR TORT, BY STATUTE OR COMMON LAW, AND YOU FURTHER AGREE TO INDEMNIFY
AND HOLD US HARMLESS FROM ALL OTHER CLAIMS (INCLUDING BUT NOT LIMITED TO CLAIMS ALLEGING
PRODUCT LIABILITY, STRICT LIABILITY, DECEPTIVE TRADE PRACTICES, BODILY INJURY, AND/OR PROPERTY
DAMAGE) TO THE MAXIMUM EXTENT PERMISSIBLE UNDER LAW).
THE EXPRESS WARRANTY PROVIDED HEREIN BY SIA IS THE SOLE AND EXCLUSIVE WARRANTY AND IS IN
LIEU OF ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE HEREBY
DISCLAIMED. EXCEPT FOR THE EXPRESS LIMITED WARRANTIES HEREIN, THE CLIMATE WIZARD COOLER IS
SOLD “AS IS, WHERE IS. NO OTHER PERSON OR ENTITY IS AUTHORIZED TO OFFER, OR GIVE YOU, ON OUR
BEHALF, ANY OTHER WARRANTY.
EXPRESS LIMITED WARRANTY TERM:
SUBJECT TO THE CONDITIONS AND EXCEPTIONS STATED HEREIN, SIA warrants the CLIMATE WIZARD COOLER sold by
SIA as follows:
1. SIA warrants the Cooler cabinet only (base, top, side panels) against corrosion due to normal operation for 1 year.
2. SIA warrants the structural integrity of all plastic components against defects in materials or workmanship for 1 year.
3. SIA warrants, for 1 year, the original factory-installed water pumps, motors, Chlorinator, Water Solenoid, Water Probe, Drain
Valve and controls against all defects in material and workmanship.
4. SIA warrants the factory installed cooler pads (cores) against de-lamination due to manufacturing defects for 1 year.
REPLACEMENT OF AIR FILTERS AND/OR COOLER PADS DUE TO NORMAL WEAR AND TEAR IS A COMMON
MAINTENANCE FUNCTION AND IS NOT COVERED BY THIS WARRANTY.
5. All labor costs incurred for installation, removal, or re-installation are the purchaser’s responsibility.
6. All shipping costs for replacement parts are the purchaser’s responsibility.
EXPRESS LIMITED WARRANTY COMMENCEMENT:
Warranty coverage begins on the installation date. The installation date is either:
(1) The date that the Cooler was originally commissioned (commissioning being the process that occurs on, or shortly after, the
Cooler is installed whereby the installer checks the installation of the Cooler, and makes any nal adjustments, before hand-over to
the purchaser). The date the Cooler was commissioned must be provided to Seeley at the time of warranty registration; or
(2) If the date the Cooler was originally commissioned cannot be veried by Seeley, the installation date shall be deemed to be the
date on the purchaser’s invoice for the purchase of the Cooler.
However, if the Cooler is not installed within 90 days of the date on the purchaser’s invoice for the purchase of the Cooler, then the
warranty coverage commences on the date that is 90 days from the date on the purchaser’s invoice.
THE DATE ON THE PURCHASER’S INVOICE FOR THE PURCHASE OF THE COOLER MUST BE GENUINE. A NON-
GENUINE DATE WILL NOT BE ACCEPTED BY SIA.
LIMITED REMEDIES:
THE EXPRESS REMEDIES PROVIDED HEREIN ARE THE SOLE AND EXCLUSIVE REMEDIES FOR ALL CLAIMS
RELATED TO THE CLIMATE WIZARD, AND ARE IN LIEU OF ALL OTHER REMEDIES, WHICH ARE HEREBY
DISCLAIMED BY SIA AND WAIVED BY YOU TO THE FULLEST EXTENT PERMISSIBLE BY LAW (INCLUDING BUT NOT
LIMITED TO WAIVER OF ALL DECEPTIVE TRADE PRACTICES STATUTES).
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 51
WARRANTY TERMS (USA)
EXPRESS LIMITED REMEDIES:
SUBJECT TO THE CONDITIONS AND EXCEPTIONS STATED HEREIN, your remedies for any claim related to the CLIMATE
WIZARD COOLER are limited to the following:
7. For breach of the foregoing Express Limited Warranty, if a claim is timely made within the applicable Relevant Warranty
Period, THE SOLE AND EXCLUSIVE REMEDY SHALL BE, AT THE OPTION OF SIA AND AT SIA’S COST, TO REPAIR/
REPLACE THE DEFECTIVE PART, REPLACE THE COOLER, OR REFUND THE PURCHASE PRICE PAID for the Climate
Wizard cooler (any such refund excluding price paid by end-user for delivery, installation, service, repairs and/or maintenance).
If SIA elects to replace or repair either parts or coolers, SIA may, in its discretion, use refurbished parts or coolers in making
the replacement or repairs, and may, in its discretion, substitute similar SIA authorized parts or coolers instead of the identical
warranted part or cooler, even if such parts or coolers are not on its current price/equipment list. You shall have no recourse for
breach of the Express Limited Warranty if written notice of claim is not received by SIA within the applicable Relevant Warranty
Period, in which case your claim shall be deemed time-barred for all purposes.
8. EXCLUSIONS FROM EXPRESS LIMITED WARRANTY. The EXPRESS LIMITED WARRANTY excludes coverage for and SIA
disclaims (and you hold harmless from and indemnify SIA against) any and all liability to or for:
9. anyone other than You or any person directly deriving title to the Climate Wizard cooler from You whilst in its original place of
installation; (i.e. this Express Limited Warranty is assignable by You only to the person or entity who directly acquires or buys
from you your business and/or property, but the assignee has no further right of assignment); and
10. normal wear and tear; and
11. the cooler’s cooling performance, eciency, water, and electricity consumption, all of which may vary widely depending upon
the environment in which the cooler is installed and operates, the area, composition and insulation of the interior structure which
it is intended to cool, and how it is used; and
12. damage, loss or claims caused by, resulting from, or arising out of any utilities, including, but not limited to, electrical surges,
and inadequacies, interruptions, failure, or other problems in or with electricity, power, or clean water supply to the cooler; and
13. damage, loss or claims caused by, resulting from, or arising out of installation, servicing, maintenance, or repair that is not
performed in accordance with SIA’s written instructions; and
14. the replacement, supply, or servicing of consumable items (including, without limitation, washers, seals, bearings, drive belts,
oat valves, plumbing components, cooler pads); and
15. calcication of the cooler pads, since calcication may be aected by minerals in the water supplied to the cooler and in the
ambient air; and
16. installation or re-installation of the cooler (including without limitation related ductwork, ttings, and other installation
components) which is the responsibility of your Supplier and/or installer; and
17. acts of God or nature, e.g., re, ood, tornado, power outage, lightning, dust storm; or acts of theft or vandalism; or any
intentional act which impairs the utility of or damages the cooler; and
18. all costs of labour and travel incurred in connection with repairing or replacing a defective part or the cooler; and
19. any costs incurred by Us in connection with a warranty claim which We determine is not a valid claim covered by the Express
Limited Warranty; and
20. personal, residential, or household use of the Climate Wizard cooler.
LOSS OF EXPRESS LIMITED WARRANTY: THE EXPRESS LIMITED WARRANTY SHALL BE NULL AND VOID, ALL
LIABILITY FOR BREACH OF SUCH WARRANTIES OR OTHERWISE SHALL BE DEEMED DISCLAIMED, AND YOU
SHALL WAIVE ALL RIGHTS AND REMEDIES OF ANY KIND FOR ANY ALLEGED DEFECT IN THE CLIMATE WIZARD
COOLER, IF:
21. the Climate Wizard cooler has not been installed and commissioned, in accordance with the instructions in the Owner’s Manual,
by a qualied, licensed, properly trained technician; OR
22. the Climate Wizard cooler has not been operated by you, and/or serviced and/or maintained by a qualied, licensed technician,
in accordance with the instructions provided in the Owner’s Manual; OR
23. you fail to maintain and present with any notice of claim the up-to-date Maintenance Schedule (if same is contained in the
Owner Manual) showing all work performed on the cooler from installation, the date of each work item, a description of the work
performed, and the name, signature and contact details of the qualied, licensed technician who performed the work; OR
24. any installation, commissioning, service or maintenance has not been properly or competently performed in accordance with
applicable electrical, plumbing, building and safety codes and regulations; OR
25. use of any replacement parts or spare parts not authorized by SIA; OR
26. addition of any third party device to (except where such addition is required by the installation instructions and complies with
those instructions), or the removal, modication, or alteration of, the Climate Wizard cooler or any SIA component thereof; OR
27. the Climate Wizard cooler has been moved from the original place of installation (whether at the same premises or to dierent
premises).
EVEN IF THE EXCLUSIVE CONTRACTUAL REMEDY (OF REPAIR, REPLACEMENT, OR REFUND OF THE PURCHASE
PRICE) PROVIDED HEREIN FAILS OF ITS ESSENTIAL PURPOSE, SIA SHALL NOT BE LIABLE TO YOU FOR ANY
CONSEQUENTIAL, INCIDENTAL, INDIRECT, PUNITIVE, EXEMPLARY, OR SPECIAL DAMAGES, INCLUDING, WITHOUT
LIMITATION, LOST REVENUES, DOWNTIME, LOSS OF USE, SUBSTITUTE EQUIPMENT, GOODWILL, DAMAGE TO OR
REPLACEMENT OF YOUR OTHER EQUIPMENT AND PROPERTY. IN NO EVENT SHALL OUR LIABILITY EXCEED THE
PURCHASE PRICE PAID FOR THE GOODS.
52 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
WARRANTY TERMS (USA)
CONDITIONS TO WARRANTY CLAIM: Failure to comply with the following conditions shall waive your warranty claim and release
and discharge Us from any liability for same.
28. NOTICE. In order to make a claim hereunder, You must send to the original Supplier of the cooler, or a cooler contractor
authorized by Us, or Us, written notice of the claim made, describing the breach claimed with particularity, stating the date
you rst learned of it, with your name, address and daytime telephone number, the address at which the Goods are installed,
and the model and serial number of the Goods, by mail or (if to Us, then you may also do this through our website (see details
below)), and the written notice (or claim lodged through our website) must be received within the Relevant Warranty Period:
• If by mail to Us, then to:
Convair Cooler Corporation dba
Seeley International (Americas)
1002 South 56th Avenue
Suite 101
Phoenix, Arizona 85043
United States of America; or
• If to Us through our website, then at:
www.seeleyinternational.com/americaswarranty
29. PROOF OF PURCHASE AND SERVICE RECORDS. You shall, in our discretion, within the Relevant Warranty Period, either
send to us at the address below, or make available for inspection by the authorized person or company who repairs or replaces
the defective part or cooler: (i) the legible and unmodied original proof of purchase, which clearly indicates the name and
address of the original retailer, the date and place of purchase, the product name or other product serial number, and show you
as the original end-user customer for the Goods, (ii) all of your records of installation, service and maintenance carried out to
the Goods, plus the up-to-date Maintenance Schedule (if same exists) in the Owner’s Manual, and (iii) your name and contact
details.
30. SAFE ACCESS TO THE GOODS. You shall provide Us, or the authorized person or company that repairs or replaces the
defective part or cooler, safe access to your premises and the specic location on your premises where the Goods are installed
so that We and/or that authorized person or company may safely access and inspect the Goods and, if a breach of warranty is
conrmed, make repairs or replace parts, whichever remedy We elect in our discretion.
DISPUTE RESOLUTION
31. GOVERNING LAW. This Limited Warranty and all disputes arising from or related to the Climate Wizard cooler sold herewith
shall be governed by the Federal Arbitration Act and the laws of the State of Denver, excluding its conicts of law rules and
excluding application of the U.N. Convention on Contracts for the International Sale of Goods.
32. FORUM. All disputes arising from or related to this Limited Warranty or the Climate Wizard cooler (including but not limited to
the validity of this arbitration clause) shall be exclusively resolved by binding arbitration conducted by an arbitrator pursuant to
the Commercial Arbitration Rules of the American Arbitration Association in Denver, Colorado. You waive the right to join your
claim with the claims of any other claimants in a class action or other proceeding, to the maximum extent that such waiver is
permissible. The courts in Denver, Colorado shall be the exclusive venue for ancillary relief in aid of arbitration, to which venue
and jurisdiction all parties consent. The arbitral award shall be nal and non-appealable and shall be enforceable in any court
of competent jurisdiction. You agree to maintain the condentiality of and not to disclose the claims made in the arbitration,
the evidence submitted therein, or the arbitral award, subject to both parties’ rights to entry of judgment upon the award by a
court of competent jurisdiction. This arbitration clause shall be binding upon all parties to a claim that relates in any way to this
Limited Warranty or the Climate Wizard cooler, including Us, You, the Supplier, and all third parties.
33. ATTORNEYS’ FEES AND COSTS. The prevailing party in any legal proceeding shall be entitled to recover its/his or her
reasonable attorneys’ fees and costs (including arbitration fees and costs paid).
34. BINDING EFFECT. This Limited Warranty is binding upon and shall inure to the benet of Convair Cooler Corporation and
its parent company, Seeley International Pty Ltd of Australia, which is the manufacturer of the Goods, and which has made
a Limited Warranty to SIA that corresponds to this Limited Warranty; and to You and any person directly acquiring title to the
Climate Wizard cooler from You whilst in its original place of installation.
MISCELLANEOUS
35. Severability. If any provision hereof is determined to be invalid or unenforceable, the remainder of this Limited Warranty shall
continue in full and eect.
36. Captions. The captions or headings used for the provisions hereof are used for convenience only and shall not be interpreted to
restrict the plain meaning of the provisions themselves.
TO CONTACT US:
Customer Service Department
Convair Cooler Corporation dba
Seeley International (Americas)
1002 South 56th Avenue
Suite 101
Phoenix, Arizona 85043
Tel: +1 (602) 353 8066
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 53
54 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
APPENDIX A
EXAMPLE WALL CONTROLLER WIRING
ILL3706
INTERMEDIATE COOLERS
FINAL COOLER
ROOM SENSOR
(OPTIONAL KIT)
BMS
LOCK
BMS
FAULT
BMS
FAULT
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 55
FIRST COOLER
WALL CONTROLLER
AMBIENT SENSOR
(OPTIONAL KIT)
BMS
FAULT
COMMUNICATION CABLE
SPECIFICATIONS
• Suitable for RS-485 applications
• Minimum 1 twisted pair (TP) and a third conductor
• Copper conductors
• 0.5 mm
2
/ AWG 20
• Braided shield with drain wire
Characteristic impedance 120Ω
• Nominal capacity between conductors 89 pF/m
• Nominal capacity between conductors and shielding 161pF/m
MODBUS RS-485 CABLE WIRING RULES
• Communication wiring must be kept separate from AC power
wiring.
• Always route communication cables at least 300mm (12”)
away from high voltage cables and high-power machines.
• Crossover high power cables at right angles.
Maximum cable length from Wall Controller / Primary to rst
cooler is 100m.
• Maximum cable length between each cooler is 100m.
• Coolers must be connected in daisy-chain style, not star or
multi-drop..
56 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
APPENDIX B
EXAMPLE LOW VOLTAGE BMS WIRING
CW-H
CW-80
BMS CONTROL
FAN SPEED
FAULT SIGNAL
0-10Vdc
BMS CONTROL WIRING EXAMPLE
DEC SELECT
IEC SELECT
COMMON
ILL3721
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 57
APPENDIX C
MODBUS REGISTERS
COMMANDS
REGISTER TYPE DESCRIPTION DETAILS
9200 UINT Commands
Bit 0 IEC Enable (Indirect Evaporative Cooling)
Bit 1 DEC Enable (Direct Evaporative Cooling)
Bit 2 Fault Reset
Bit 3 Manual Drain
Bit 4-15 NOT USED
9201 UINT Supply Fan Speed 0 - 1000 (0 to 100%) * 10 Minimum value of 200 needed to start the fan.
IEC or DEC inputs also require a Fan Speed input to start the watering cycles.
STATUS
9205 UINT Status
Bit 0 FAULT
Bit 1 Low Probe WET
Bit 2 High Probe WET
Bit 3 Inlet Solenoid OPEN
Bit 4 Drain Valve OPEN
Bit 5 Indirect Pump RUNNING
Bit 6 Direct Pump RUNNING
Bit 7 Chlorinator RUNNING
9206 UINT Supply Fan Speed 0 - 100 0 – 100%
9207 UINT Salinity of Tank 0 - 6615 Water Salinity Level (uS/cm)
9208 UINT Chlorinator PWM 0 – 100 0 – 100% Output of the chlorinator
9209 UINT Fault Code Fault Code. If multiple faults are present, the fault codes will cycle.
9210 INT Sensor Input 1 Value Sensor Valves depend on sensor type
Temperature
o
C /10 or
o
F/10
Relative Humidity %/10
Pressure Pa or inwg/100
9211 INT Sensor Input 2 Value
9212 INT Sensor Input 3 Value
9213 INT Sensor Input 4 Value
58 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J
APPENDIX D
BACNET OBJECT LIST
CONTROL
Object Name Object Type & Identier Details
BCN_CMD_IEC Binary-value 0 IEC Enable (Indirect Evaporative Cooling)
BCN_CMD_DEC Binary-value 1 DEC Enable (Direct Evaporative Cooling)
BCN_CMD_Spd Analogue-value 0 0 to 10 Fan Speed
BCN_CMD_Drain Binary-value 2 Manual Drain
BCN_CMD_ON_OFF Binary-value 14 Cooler Run
BCN_CMD_FaultReset Binary-value 4 Reset Fault Codes
BCNIntegrity Binary-value 13 BACnet Integrity - See Notes.
RTCYear Analogue-value 1 Range 00 to 99
RTCMonth Analogue-value 2 Range 1 to 12
RTCDay Analogue-value 3 Range 1 to 31
RTCHour Analogue-value 4 Range 0 to 23
RTCMinute Analogue-value 5 Range 0 to 59
RTCSecond Analogue-value 6 Range 0 to 59
RTCDay Of Week Analogue-value 7 Range 0 to 6 (0 = Sunday)
BCN_CMD_RTCSet Binary-value 3 Set Time & Date
MONITORING
Object Name Object Type & Identier Details
STSIEC Binary-value 5 IEC Pumps RUNNING
STSDEC Binary-value 6 DEC Pumps RUNNING
STSERROR Binary-value 7 Fault
STSLowProbe Binary-value 8 Low Probe WET
STSHighProbe Binary-value 9 High Prbe WET
STSSolenoid Binary-value 10 Inlet Solenoid OPEN
STSDrain Binary-value 11 Drain Valve OPEN
STSChlorinator Binary-value 12 Chlorinator RUNNING
STSSupplyFSpd Analogue-input 8 Supply Fan Speed Range 0 to 10
STSSalinity Analogue-input 9 Water Salinity Level (uS/cm)
STSChlPWM Analogue-input 10 Chlorinator PWM % (CW-H only)
STSFaultCode Analogue-input 11 Fault Code. If multiple faults are present, the fault codes will cycle.
STSExhaustFSpd Analogue-input 12 Exhaust fan speed (Vdc) (CW-80 only)
STSSensor1 Analogue-input 13 Sensor Valves depend on sensor type
Ambient Sensor Temperature -40 to 70
o
C or -40 to 158
o
F
Ambient Sensor Relative Humidity 0 to 100 %
Room Sensor Temperature 0 to 100
o
C or 32 to 212
o
F
Room Sensor Relative Humidity 0 to 100 %
Duct Sensor Temperature 0 to 100
o
C or 32 to 212
o
F
Duct Sensor Relative Humidity 0 to 100 %
Pressure Sensor 0 to 500Pa or 0 to 2.00 inwg
(STSSensor5 and STSSensor6 are CW-80 only)
STSSensor2 Analogue-input 14
STSSensor3 Analogue-input 15
STSSensor4 Analogue-input 16
STSSensor5 Analogue-input 17
STSSensor6 Analogue-input 18
IEC or DEC inputs also require a Fan Speed input to run.
BACnet Integrity - Object resets every 5 seconds. Users must write to this object at least once every 30 minutes to avoid Fault Code 16
RTC analogue values can only be adjusted whilst “RTCSet” is active.
Metric or Imperial units are dependent upon the units selected on the Multi-Magic PLC Settings page.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-J | 59
Ax serial & model
number sticker here
2403
857749-J
Software 89R0224
Warranty Service
Australia: 1300 650 644
New Zealand: 0800 589 151
Seeley International Technical Support
Australia: 1300 650 399
New Zealand: 0800 589 152
For all other regions, contact your local distributor:
seeleyinternational.com
Online Support Portal (AUS/NZ)
Scan or Click QR Code
It is the policy of Seeley International to introduce continuous product improvement.
Accordingly, specications are subject to change without notice.
Please consult with your dealer to conrm the specications of the model selected.