LISTED
540H
3MWire Connector
T/R+ (Tan/Red)
Data Sheet
Application
Use a 3M
Wire Connector T/R+ to electrically
connect two or more conductor ends in a pigtail
application and insulate the connection.
Wire
AWG Range: COPPER conductors only, No. 22 thru
No. 8 solid and/or stranded (see wire matrix for
specific wire combinations).
METRIC Range: COPPER conductors only, 0,5 mm
2
thru
6,0 mm
2
ridged (solid) and flexible (stranded).
Construction
Spring - Spring steel, corrosion resistant coating
Insulator: - Flame retardant, polypropylene, tan and
thermoplastic elastomer, red
Weight
.0068 lbs. (3.1 g)
Performance Test
The following tests were performed to the specification
of UL Standard 486C and CSA Standard C22.2 No. 188-
M1983.
Static-Heating
Pass
Secureness
Pass
Pullout
Pass
Dielectric Voltage Withstand
Pass
Secureness-of-Insulation
Pass
Flammability
Pass
Wire Connector Canadian Standards
Association
Standard NO. 22.2
NO. 188-M1983
3M File NO. LR15503
Other Tests:
per MIL-STD-1344A
Method 2005.1UV Exposure
Pass
Per ASTM G-53-77 Salt Spray
Pass
Fluid Immersion Test
Connectors were immersed in the following chemicals
for seven days at 23˚C±2˚C with no affect on
appearance or loss of material strength.
Typical Reagents and Materials
From ASTM D 543-87 and MIL-STD-1344A
Acetic Acid
Acetone
Detergent Solution, Heavy Duty
Ethyl Alcohol (95%)
Ethyl Alcohol (50%)
Heptane
Hydrogen Peroxide Solution 28%
Methyl Alcohol
Sodium Hydroxide Solution
Mineral Spirit
Lubricating Oil
Engineering Specification
3M Wire Connector T/R+ is capable of connecting two
or more wires in a pigtail application, in the wire range
of No. 22 thru No. 8 AWG solid and/or stranded
copper conductors. The connector shall be constructed
of an active (live) spring with a corrosion resistant
coating. The connector shall be UL LISTED and CSA
Certified as a pressure wire connector. The connector
shall be voltage rated 600 volts maximum building wire
and 1000 volts maximum signs and lighting fixtures
(luminaries). The connector shall have a maximum
operating temperature of 105˚C (221˚F).
How to read this chart:
1
No. 18 str
+
4 No. 20 solid or str
(5 total)
Example 2:
1
No. 12 sol
+
2 No. 12 str
(3 total)
3M™ Wire Connector T/R+
AWG Wire Combinations
Copper to Copper Conductors
Installation Instructions
CAUTION
Working around energized systems may cause serious injury or
death. Installation should be performed by personnel familiar with
good safety practice in handling electrical equipment. De-energize
and ground all electrical systems before installing product.
!
1. Strip wire insulation 1/2”.
2. Firmly grasp wires, making sure insulation ends
are even and tightly bundled. (Wires may be
twisted or untwisted.) Lead stranded wires
slightly. Slip the connector over wire tips.
3. Turn connector onto wires in clockwise
direction until secure.
4. To remove, turn connector counter- clockwise.
Regulatory Agencies
UL Listed as a Pressure Cable Connector
Tested per UL Standard 486C
UL File No. E23438
Operating Temperature: 105˚C (221˚F)
Voltage Rating: 600 volts max. building wire;
1000 volts max. signs and fixtures Flammability
Rating: UL94 V-2
CSA Certified-CSA Standard C22.2 No. 0,
188-M1983
CSA File No. LR15503
Operating Temperature: 105˚C (221˚F)
Voltage Rating: 600 volts max. building wire 1000
volts max. signs and luminaires.
Flammability Rating: C22.2 No. 0.6 V-2
Operating Temperature: 105˚C (221˚F)
Voltage Rating: 600 volts max. building wire;
1000 volts max. signs and fixtures Flammability
Rating: UL94 V-2
Federal Specification W-S-610:
“Commercial package only”
Type
Class
Kind
Style
1
1
Cu
G
Metric Wire Combinations
Copper Conductors Only
Cross Section Capacity
Minimum Maximum
2.0mm
2
12.5mm
2
Conductor Combinations
Quantity
Size
Type
6
0,5mm
2
sol/str
3-6
0,75mm
2
sol/str
2-6
1,0mm
2
sol/str
2-6
1,5mm
2
sol/str
2.5
2,5mm
2
sol/str
2.3
4.0 mm
2
sol/str
Only AWG combinations are UL Listed or CSA Certified.
3M is a trademark of 3M Company.
is a trademark of Underwriters Laboratories.
is a trademark of Canadian Standards Association.
Important Notice
All statements, technical information, and recommendations related to 3M’s products are based
on information believed to be reliable, but the accuracy or completeness is not guaranteed.
Before using this product, you must evaluate it and determine if it is suitable for your intended
application. You assume all risks and liability associated with such use. Any statements related to
the product, which are not contained in 3M’s current publications, or any contrary statements
contained on your purchase order, shall have no force or effect unless expressly agreed upon, in
writing, by an authorized officer of 3M.
Warranty; Limited
Remedy; Limited
Liability
This product will be free from defects in material and manufacture at the time of purchase. 3M
MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this
product is defective within the warranty period stated above, your exclusive remedy shall be, at
3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M
product. Except where prohibited by law, 3M will not be liable for any direct, indirect, special,
incidental or consequential loss or damage arising from this 3M product, regardless of the legal
theory asserted.
Electrical Markets Division
Austin, TX
Phone: 800-245-3573
www.3M.com/electrical
Please Recycle. Printed in USA.
© 3M 2019. All Rights Reserved.
78-8126-0603-0 Rev B