30 Low Voltage Products & Systems
1SXU210206G0201 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Tmax molded case circuit breakers
Example:
Characteristics of the plant:
• Type of network: one terminal grounded (the negative one)
• Network voltage: Vn = 250 VDC
• Rated voltage absorbed by the loads (Ib): 450 A
• Short-circuit current: 40k A
Choice of the circuit breaker
According to the indications on page 23, to correctly size
the circuit breaker, the following must be complied with:
• Ve ≥ Vn
• Icu ≥ Ik
• In ≥ Ib
With reference to the type of network, the suitable table
shall be identified from tables 6-7-8. In this case, the table
for a network with one grounded terminal (Table 7) shall be
chosen.
The column with the performances for a network voltage
higher than or equal to the plant voltage shall be identified,
in this example Vn≥ 250 VDC.
The load current is used to identify the row of the table for
circuit breakers with uninterrupted rated current Iu higher
than or equal to the load current. In this case, a Tmax T5
with Iu=600 A circuit breaker can be used.
The interrupting rating is chosen according to the relation
Icu≥Ik. In this example, since Ik=40 kA, version S can be
used.
With these limitations, two possible schemes for the pole
connection can be identified. Assuming that the grounded
terminal is to be disconnected also, the connection scheme
to be used is the following:
LOAD
A 500 A T5S thermal magnetic circuit breaker shall be cho-
sen. To summarize, a three-pole thermal magnetic T5S600
TMA 500 circuit breaker shall be used connected as shown
in the figure, i.e. with two poles in series on the terminal
insulated from ground and the other one connected to the
grounded terminal.
Emax air circuit breakers
Example:
Characteristics of the plant:
• Type of network: insulated
• Network voltage: Vn = 500 VDC
• Rated voltage absorbed by the loads (Ib): 1800 A
• Short-circuit current: 45 kA
Choice of the circuit breaker
According to the indications on page 23, to correctly size
the circuit breaker, the following must be complied with:
• Ve ≥ Vn
• Icu ≥ Ik
• In ≥ Ib
With reference to the type of network, the suitable table
shall be identified from tables 9-10-11. In this case, the
table for an insulated network (Table 9) shall be chosen.
The column with the performances for a network voltage
higher than or equal to the plant voltage shall be identified,
in this example Vn≥ 500 VDC.
According to the column considered, the circuit breaker
which would seem suitable under short-circuit conditions
is an E2N (N=50kA>Ik). However, according to the table of
the rated uninterrupted current (page 39), it is necessary to
pass to an E3N since it has Iu= 2000 A which is higher than
the current absorbed by the loads. In this way, the third
relationship is complied with.
Therefore the suitable circuit breaker is a three-pole E3N
2000 circuit breaker with PR1122-123/DC In=2000 A. The
connection of the poles is carried out in the factory by ABB.
The solution of the table shows the connections between
three-pole circuit breaker, load and supply source.
LOAD
LOAD
Choice of the protective device